ML19318C559
| ML19318C559 | |
| Person / Time | |
|---|---|
| Site: | Crane |
| Issue date: | 06/12/1980 |
| From: | Reid R Office of Nuclear Reactor Regulation |
| To: | Arnold R METROPOLITAN EDISON CO. |
| References | |
| NUDOCS 8007020019 | |
| Download: ML19318C559 (12) | |
Text
o UNITED STATES v
g
[
p, NUCLEAR RcGULATORY COMMISSION l
j wash NGTON, D. C. 20555 k,...../
June 12, 1980 Docket No. 50-289 Mr. R. C. Arnold Senior Vice President Metropolitan Edison Cogany 100 Interpace Parkway Parsippany, New Jersey 07054 J
Dear Mr. Arnold:
Recent restrictions and reduced allocations at comercial burial sites have caused numerous licensees to actively consider increased on-site storage.
Several licensees are currently storing waste on a temporary basis and pro-posing to establish new facilities for longer term storage.
If on-site storage is necessary, the licensee must assure that the design and operation of the proposed facilities are adequate to maintain public health and safety, minimal risk to operating personnel, and present a minimal environmental igact.
Any decision to incorporate on-site storapa requires a 10 CFR 50.59 safety review of the areas of:
(1) Radioactive Material and Effluent Control, (2)
Radiation Dose Control for Both On-site and Off-site Individuals, and (3) Acci-i dent Prevention and Control. Enclosed is a draft NRC Licensing Position for
" Safety Considerations for Temporary On-Site Storage". This draft is forwarded for your information and use in evaluating low-level waste storage criteria.
The NRC is presently evaluating both temporary and long term on-site storage and its implications. Currently,10 CFR 50.59 requires that you furnish a report containing a brief description and summary of the safety evaluation for each 10 CFR 50.59 change to your facility. The proposed model Appendix I generic Techni-cal Specifications (NUREG-0472 and 0473) contained guidance on the desired detail necessary in that report for radwaste systems.
In the interim, until Appendix I Technical Specifications are incorporated in your operating license, you are requested to 'nclude reviews for on-site storage additions in the monthly oper-ating report following the period in which the evaluation was cogleted. This report should detail '.he major additions / changes and contain a summary of the safety evaluation. Inis summary should include as a minimum your evaluation of each of the safety review areas described herein, including consideration of the guidance provided in the enclosed draft Licensing Position, man-rem inacts, anticipated radiological release assessments, final disposition of waste, and final conclusion of the 50.59 evaluation.
l 8 00702 0 OR 3
e Mr. R. C. Arnold L No foral response is required concerning this letter unless waste storage facili-ties are modified. Conments, however, are invited concerning the enclosed draft Licensing Position.
Sincerely, W AM Robert W. Reid, Chief Operating Reactors Branch #4 Division of Licensing
Enclosure:
Draft Licensing Position cc w/ enclosure:
See next page
?
1 l
N k
Metropolitan Edison Company Wal r H. J rdan Oak Ridge Tennessee 37830 ccw/ enclosure (s):
- Mr. Marvin I. Lewis Dr. Linda W. Little 6504 Bradford Terrace 5000 Hermitage Drive P,hiladelphia, Pennsylvania 19149 Raleigh, North Carolina 27612 Walter W. Cohen, Cons emer Advocate Holly S. Eeck Department of Justice Anti-Nuclear Group Representing Strawberry Sc,aare,14th Floor York Harrisburg, Pennsylvania 17127 245 W. Philadelphia Street York, Pennsylvania 17404 R:bert L. Knupp, Esq.
Assistant Solicitor John Levin, Esq.
Knupp and Andrews Pennsylvania Public Utilities Com.
P.O. Box P Box 3265 407 N. Front Street Harrisburg, Pennsylvania 17120 Harrisburg, Pennsylvania 17108 Jordan D. Cunningham, Esq.
John E. Minnich, Chairman Fox, Farr and Cunningham Dauphin Co. Board of Comissioners 2320 North 2nd Street Dauphin County Courthouse Harrisburg, Pennsylvania 17110 Front and Market Sts.
Harrisburg, Pennsylvania.17101 Theodore A. Adler, Esq.
WIDOFF REAGER SELK0WITZ & ADLER Atomic Safety and Licensing Appeal Board Post Office Box 1547 0
U.S. Nuclear Regulatory Commission Harrisburg, Pennsylvania 17105 Washington, D. C.
20555 Ms. Marjorie M. Aamodt o Atomic Safety and Licensing Board Panel R.D. #5 U.S. Nuclear Regulatory Commission Coatesville, Pennsylvania 19320 Washington, D. C.
20555 Ms. Karen Sheldon o Docketing and Service Section Sheldon, Harmon, Roisman & Weiss 1725 I Street, N. W.
U.S. Nuclear Regulatory Commission Suite 506 Washington, D. C.
20555 Washington, D. C.
20006 R:bert Q. Pollard Earl B. Hoffman Chesapeak Energy Alliance Dauphin County-Comissioner 609 Montpelier Street Dauphin County Courthouse Baltimore, Maryland 21218 Front and Market Streets Harrisburg, Pennsylvania 17101 Chauncey Kepford Judith H. Johnsrud Ellyn Weiss. Esq.
Environmental Coalition on Nuclear Power Sheldon Harmon, Roisman & Weiss 433 Orlando Avenue 1725I5treet,N.W.
State College, Pennsylvania 16801
$$n n
D.C.
20006 Ms. Frieda Berryhill, Chairman Mr. Steven C. Sholly C alition for Nuclear Power Plant 304 South Market Street I
Postponement Mechanicsburg, Pennsylvania 17055 2610 Grendon Drive Wilmington, Delaware 19808 Mr. Thomas Gerusky Bureau of Radiation Protection Mrs. Rhoda D. Carr 1402 Marene Drive Department of Environmental Resouices P.O. Box 2063 Harrisburg, Pennsylvania 17109 Harrisburg, Pennsylvania 17120
~
Metr:politan Edison Company Karin W. Cartsr, Esq.
505 Executive House Mr. G. P. Miller P. O. Box 2357 Mr. R. F. Wtison Harrisburg, Pennsylvania 17120 Mr. J. J. Parton Metropolitan Edison Company Honorable Mark Cohen P. O. Box 480 512 E-3 Main Capital Building Middletcwn, Pennsylvania 17057 Harrisburg, Pennsylvania 17120 G. F. Trowbridge, Esquire Dauphin County Office Emergency Shaw,. Pittman, Potts & Trowbridge Preparedness 1800 M Street, N.W.
Court House, Room 7 Washington, D. C.
20036 Front & Market Streets Harrisburg, Pennsylvania 17101 Mr. E. G. Wallace Licensing Manager Department of Environmental Resources 3'kepc V
t on ATTN: Director, Office of Radiological n
P e
Parsippany, New Jersey 07054 Post Offi e ox 2063 Harrisburg, Pennsylvania 17105 Pennsylvania Electric Company Mr. R. W. Conrad Director, Technical Assessment Vice President, Generation Division 1001 Broad Street Office of Radiation Programs Johnstown, Pennsylvania 15907 (AW-459)
U. S. Environmental Protection Agency Miss Mary V. Southard, Chairman Crystal Mall #2 Citizens for a Safe Environment Arlington, Virginia 20460 Post Office Box 405 Harrisburg, Pennsylvania 17108 Mr. Robert B. Borsum Babcock & Wilcox Government Publications Section Nuclear Power Generation Division State of Library of Pennsylvania Suite 420, 7735 Old Georgetown Road Box 1601 (Education Building)
Bethesda, Maryland 20014 Harrisburg, Pennsylvania 17126
- Ivan W. Smith, Esq.
Mr. David D. Maxwell, Chairman Atomic Safety & Licensing Board Panel Board of Supervisors U.S. Nuclear Regulatory Commission Londonderry Township Washington, D. C.
20555 RFD#1 - Geyers Church Road tiiddletown, Pennsylvania 17057 Ms. Kathy McCaughin Three Mile Island Alert, Inc.
U. S. Environmental Protection Agency 23 South 21st Street Region III Office Harrisburg, Pennsylvania 17104 ATTN:
EIS COORDINATOR Curtis Building (Sixth Floor)
Mr. L. N. Harding 6th and Walnut Streets Supervisor of Licensing Philadelphia, Pennsylvania 19106 Metropolitan Edison Company Mr. J. G. Herbein P. O. Box 480 Vice President-Nuclear Operations Middletown, Pennsylvania 17057 Metropolitan Edison Compary P. O. Box 480 Middletown, Pennsylvania 17057 l
Ms. Jane Lee i
R.D. 3; Box 3521 l
Etters, Pennsylvania 17319 1
.n.
-~
Metropolitan Edison Company.
Mr. R. J. Toole S
Manager, TMI-1 Governor's Office of State Planning Metropolitan Edison Company P. O. Box 480 and Development Middletown, PA 17057 ATTN: Coordinator, Pennsylvania State Clearinghouse Mr. W. E. Potts P. O. Box 1323 Radiological Controls Manager, TMI-1 Harrisburg, Pennsylvania 17120 Metropolitan Edison Company P. O. Box 480.
Middletown, PA 17057 Mr. I. R. Finfrock, Jr.
Jersey Central Power & Light Company Madison Avenue at Punch Bowl Road Morristown, New Jersey 07950 J. B. Lieberman, Esq.
Berlock, Israel, Lieberman 26 Broadway New York, NY 10004 Mr. J. J. Colitz Plant Engineering Manager, TMI-1 Metropolitan Edison Company P. O. Box 480 Middletown, Pennsylvania 17057 York College of Pennsylvania Country Club Road York, Pennsylvania 17405 Mr. G K. Hovey Director,, TMI-2 Metropolitan Edison Company P, 0, Box 480 Middletown, PA 17057 Mr. B. Elam Manager, Plant Engineering, Unit 2 Metropolitan Edison Company P. O. Box 480 Middletown, PA 17057 Mr. Richard Roberts The Patriot 812 Market Street Harrisburg, PA 17105 l
Mr. R. W. Heward Menager, Radiological Control, Unit 2 Metropolitan Edison Company P. O. Box 480 Middletown, Pennsylvania 17057 t
i
/
w:g[*
UNITED STATES g
(
e g
NUCLEAR REGULATORY COMMISSION g,Qj j WASMNGTON, D. C. 20555
, s., *.JJ SAFETY CONSIDERATIONS FOR TEMPORARY ON-SITE STORAGE OF LOW LEVEL RADIOACTIVE WASTE i
I.
Introduction The objective of this technical position is to provide guidance to the Licensees considering additional on-site low level radioactive waste stor-age capabilities. The duration of the intended storage, the type and form of waste, and the magnitude of radionuclides present will dictate the safe-guards and the level of complexity required to assure public health and safety, and minimal risk to operating personnel. The longer the intended storage period, the greater the degree of controls that will be required for radiation protection and accident prevention.
For purposes of this i
document, the duration of temporary material storage is to be up to four (4) years. The magnitude of the on-site storage safety hazard is predi-I cated on the type of waste being stored, the amount of radionuclides pres-ent, and how readily they might be transported into the environment.
In general, it is preferable to store radioactive material in solid form.
Under some circumstances, however, temporary storage in a liquid form may be desirable or required. The specific design and operation of any storage facility will be significantly influenced by the various waste forms, consequently, this document addresses wet waste, solidified wet waste and dry low level radioactive waste.
II.
General Information Prior to any implementation of additional on-site storage, substantial safety reviews and environmental analysis need to be conducted to assure adequate public health and safety, and minimal environmental impact. The acceptance criteria and perfomance objectives of any proposed storage facility, or area, will need to meet minimal requirements in areas of design considerations, operational considerations, safety considerations and policy considerations.
For purposes of this branch position the major emphasis will be on safety considerations in the storing, handling and eventual disposition of the radioactive waste. Design and operational acceptability will be based on minimal requirements which are defined in existing SRP's, Regulatory Guides, and industry standards for proper management of radioactive waste, policy considerations for waste min ~
imization and volume reduction will also have to be integrated into the waste manegement plan and the on-site storage alternative. Additional considerations for ALARA, decontamination, and decommissioning of the temporary storage facility also need to be integrated into the design and operation of the proposed waste storage facility.
Integration of waste I
"~
m e@$ais-a g e
o em 4 i wm.e aw,4 g
e em 9
g_
DRMT
~
~
volume reduction and eventual disposal should be performed as early as possible because future requirements for waste forms may make stored wastes unacceptable for final disposition.
III. Wet Radioactive Waste Storage (a) Wet radioactive waste will be defined as any liquid or liquid / solid slurry.
For storage considerations, wet waste is further defined as any waste which does not meet January 1,1981 burial requirements for solidified waste (i.e., < 0.5% free water by) volume of container or
< l.0 gallon per container whichever is less.
(b) The facility, supporting structure and tanks should be designed to prevent uncontrolled releases of radioactive materials due to spil-lage or accident conditions.
(c) The following design objectives and criteria are applicable for wet radioactive waste facilities.
(1) Structures that house liquid radwaste storage tanks should be designed to seismic criteria as defined l
in Standard Review Plan (NUREG 75/087 - Section 11.2).
l Foundations and walls shall also be designed and fabricated to contain the liquid inventory which might be released during a container / tank failure.
(2) All tanks or containers should be designed to withstand the corrosive n'ature of the wet waste stored.
The dur ation of storage under which the corrosive condi-tions exist shall also be considered in the design.
(3) All storage structures.should have. arbs or elevated thresholds with floor drains and sumps to safely col-lect wet wa.ste assuming the failure of all tanks or con-tainers.
Provisions should be incorporated to route spilled wet waste to the radwaste treatment systems.
(4) All tanks and containers shall have provisions to monitor liquid levels and to alann potential overflow conditions.
l (5) The quantity of radioactive material allowed and the shielding configurations will be dictated by the dose rate criteria for both the site boundary and unrestrict-ed areas on-site. The 40 CFR 190 limits will restrict the annual dose from direct radiation and effluent re-lease to the Public (indfvidual) to less than 25 mrem per year to the whole body from all sources of the Ura; nium Tuel cycle; therefore, off-site doses from on-site
s
~
~
DRAFT
! f storage must be sufficiently low to account for other sources (e.g., < 1 mrem / year). On-site dose limits as-sociated with temporary storage will be controlled per 10 CFR Part 20 including the ALARA principle of 10 CFR 20.1.
(6) All potential release pathways of radionuclides (e.g.,
evolved gases, breach of container, etc.) shall be con-troiled and monitored as per 10 CFR 50 Appendix A (General Design Criteria 60 and 64). Surveillance pro-grams should incorporate adequate methods for monitor-4 ing breach of container integrity or accidental releases.
(7) All temporarily stored wet waste will require additional reprocessing prior to shipment off-site; therefore, pro-vision should be established to integrate the required treatment with the vaste processing and solidification systems. The interface and associated systems should l
be designed and tested in accor fance with the codes and standards described in NUREG-75/087 Section 11.
IV. Solidified Radioactive Waste Storage (a) Solidified radwaste for storage purposes shall be defined as that waste which meets January 1,1981 burial site solidific f waste criteria. Therefore, solidified radwaste will be identified as wat waste (e.g., evapora, tion bottoms, resins, and sludge) which is solidified and contains < 0.5% free water (by container volume) or 1.0 gallon of liquid (in the container), whichever is less.
For purposes of this document resins or filter sludges dewatered to the above criteria will be defired under this waste classification /
criterie (b) Dewatered resins and filter media with radioactivity levels above 1 uCf/cc (>5 yr. half-life) which are disposed of after July 1,1981, will be required to be solidified or stored in hi;5 integrity containers (e.g., reinforced concrete).
Any stc. rage plans should address container protection as weil as any reprocessing requirements for eventual ship-ment and burial.
(c) Casks, tanks, and liners containing solidified radioactive waste should be designed with good engineering judgment to preclude or reduce the occurrence of uncontrolled releases of radioactive materials due to handling, transporting or storage. Accident miti-gation and control for design basis events (e.g., fire, flooding, tornadoes, etc.) must be evaluated and protected against unless otherwise justified.
7
~
Und I (d) The following design objectives and criteria are app! feable for solidified waste storage containers and facilities:
(1) All solidified radwaste should be located in restrict-ed areas where effective material control account-ability can be maintained. While structures are not required to meet seismic criteria, protection should be afforded to insure the radioactivity is contained safely
' by use of good engineering judgment, such as the use of curbs and drains to contain spills of dewatered resins or sludges.
(2) Container material selection should conform to require-ments established in NUREG-75/087 (Section 11).
If liquids exist which are corrosive, proven provisions should be made to protect the container (i.e., special liners or coatings) and, or neutralize the excess liq-uids.
If deemed appropriate and necessary, t.ighly non-corrosive materials (e.g., stainless steel) should be used. Potential corrosion between the solid waste forms and the container should also be considered.
In the l
case of dewatered resins, highly corrosive acids and bases can be generated which will significantly reduce the longevity of the container. The Process Control Program (PCP), should implement steps to assure the above does not, occur, and provisions on container materi-al selection and precoating should be made to insure that container breach does not occur during temporary storage periods.
(3) Potential release pathways of all radionuclides present in the solidified waste form shall be monitored as per 10 CFR 50 Appendix A.
Surveillance programs shall in-corporate adequate methods for detecting failure or con-tainer integrity and measuring releases to the environ-ment. For outside storage, periodic direct radiation and surface contamination monitoring shall be conducted to in-sure that levels are below limits specified in 10 CFR 20.202, 20.205, and 49 CFR 173.397. All containers should be decontaminated to these levels or below before storage.
l (4) Provision should be mr de for additional reprocessing or repackaging due to ct, stainer failure and/or, as required for final transporting and burial as per DOT and burial e
site criteria.
Contamination isolation and decontamina-tion capabilities should be developed. Whereby signifi-cant handling and personnel exposure can be anticipated, ALARA methodology should be incorporated as per Regulatory Guides 8.8 and 8.10.
_ ~
~
NN. -,
g
. (5) Procedures should be developed and implemented for early detection, prevention and mitigation of acci-dents (e.g., fires). Storage areas and facility de-signs should incorporate good engineering features and contingencies so as to handle accidents and provide safe-guard systems such as fire detectors and suppression systems. (e.g., smoke detector and sprinklers), person-
. nel training and administrative procedures to insure.
both control of radioactive materials and minimum personnel exposures. Fire suppression devices may not be necessary if combustible materials are minimal in the area.
(6)
Provisions should be incorporated for collecing liquid drainage including provisions M nmpling all col-lected liquids.
Routing of '.he colleried liquids should be to radwaste systems if contaminatica is Acected or to normal discharge pathways if the water incress was from external sources and remained unconta'minated.
(7)
Low level solidified waste stored in outside areas should be held securely by installed hold down systems.
The hold down system should secure all containers dur-ing severe environmental conditions up to and includ-ing the design basis event for this waste storage facility.
(8) Container integrity should be assured against cor-rosion from the external environment; external weather 1
protection should be included where necessary and prac-tical. Storage containers should be raised off storage pads where water accumulation can be expected to cause external corrosion and.possible degradation of container integrity.
(9) The quantity of radioactive material allowed and the shielding configurations will be dictated by the dose-rate criteria for both the site boundary and unrestrict-ed area on-site. The 40 CFR 190 limits will restrict the annual dose from direct radiation and. effluent re-leases to the Public (individual) to less than 25 mrem i
per year to the whole body from all sources of the Ura-nium fuel cycle'; therefore, off-site doses from on-site storage must be sufficiently low to account for other sources (e.g., < 1 mrsm/ year). On-site dose limits as-sociated to temporary storage will be controlled per 10 CFR Part 20 including the ALARA principle of 10 CFR 20.1.
t
. (10)
Total curie limits should be established based on the design of the storage area and the safety features provided.
(11)
Inventory records of waste types, contents, dates.cf storage, shipment, etc., should be maintained.
V.
Low Level Dry Waste storage (a) Low level dry waste is classified as contaminated material (e.g.,
paper, trash, air filters) which contains sources of radioactive material that is dispersed in small concentrations throughout large volumes of inert material which contain no free water.
Generally, this consists of dry material such as rags, clothing, cor.taminated materials and small equipment (i.e., tools and in-struments) which cannot be easily decontaminated.
(b) Licensees should implement controls to segregate and minimize the generation of Low Level Dry Waste to lessen the impact on waste storage.
Integration of Volume Reduction (VR) hardware should be considered to minimize the need for additional waste storage fa-cilities.
(c) The following design objectives and criteria are applicable for low level dry waste storage containers and facilities.
(1)
All dry or compacted radwaste should be located in re-stricted areas where effective material control and accountability can be maintained. While structures are not required to meet seismic criteria, protection should be afforded to insure the radioactivity is contained safe-
~
ly by use of good engineering judgment.
(2)
The waste container should be designed to insure radio-active material containment during normal and abnormal occurrences. The waste container materials should not support combustion. The packaged material should not l
cause fires through, spontaneous chemical reactions, re-l tained heat, etc.
(3)
Potential release pathways of all radionuclides present in the solidified waste form shall be monitored as per 10 CFR 50 Appendix A.
Surveillance programs shall in-corporate adequate methods for detecting failure of con-tainer integrity and measuring releases to the environ-l ment.
For outside storage periodic direct radiation and surface contamination monitoring shall be conducted to in-l sure that levels are below limits specific in 10 CFR l
20.202, 20.205, and 49 CFR 173.397. All containers should be decontaminated to these levels or below before storage.
ggq 7-I (4) Containers should generally comply with the criteria of 10 CFR 71 and 49 CFR 170 to minimize the need for repackaging for shipment.
(5) ' Increased container handling and personnel exposure can be anticipated, consequently, all ALARA meth.
odology should be incorporated per Regulatory Guide 8.8
. and 8.10.
(6) The quantity of radioactive material allowed and the shielding configurations will be dictated by the dose-rate criteria for both the site boundary and unre-stricted areas on-site. The 40 CFR 190 limits will re-strict the annual dose from direct radiation and ef-fluent release to the Public (individual) to less than j
25 mrem per year to the whole body from all sources of the Uranium fuel cycle; therefore, off-site doses from on-site storage must be sufficiently low to account for other sources (e.g., < 1 mrem / year).
On-site dose limits associated to temporary storage will be control-led per 10 CFR Part 20 including the ALARA principle of 10 CFR 20.1.
(7) Total curie limits should be established based on the design of the storage area and the safety features provided.
(8) Provisions should be incorporated for collecting liq-uid drainage including provisions for sampling all col-lected liquids. Routing of the collected liquids should be to radwaste sy:tems if contamination is detected or to normal discharge pathways if the water ingress was from external sources (e.g., rain water or moisture) and remained uncontaminated.
(9)
Low-level waste stored in outside areas should be held securely by installed hold down systems. The hold down system should secure all containers during severe en-vironmental conditions up to and including the design 1
basis event for this waste storage facility.
(10)
Container corrosion should be assured against from both the internal and external environment. Special internal liners and external weather protection should.be in-cluded where necessary and practical. Storage containers should be raised off storage pads where water accumula-tion can cause external corrosion and resultant loss of container integrity.
(11)
Inventory records of waste types, content, dates of storage, shipment, etc., should be maintained.
w
+ - - - - - - -
--,e
-,p.
..._,y
__.,-,._m-_-,,-w
-w m
-