ML19318A081

From kanterella
Jump to navigation Jump to search
Forwards LER 80-028/03L-0
Date released: 11/28/2019 Download: ML19318A081


LER 80-028/03L-0:on 800515,during Performance of Routine Test,Diesel Generator 12 Failed to Reach Rated Speed in Less than 10-s Until Third Attempt.Caused by Intermittent Female Pin & Crack in Bakelite Spacer of Anphenol Connector
ML19318A091
Person / Time
Site: Calvert Cliffs 
Issue date: 06/13/1980
From: Bauer E, Heibel R
BALTIMORE GAS & ELECTRIC CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML19318A091 (2)
Forwards LER 80-028/03L-0
ML19318A080
Person / Time
Site: Calvert Cliffs 
Issue date: 06/13/1980
From: Russell L
BALTIMORE GAS & ELECTRIC CO.
To: GRIER B H
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
Download: ML19318A080 (1)