ML19317H425

From kanterella
Jump to navigation Jump to search
Forwards Request for Addl Info Re Review of 791005 & s Concerning Adequacy of Station Electric Distribution Sys Voltages.Response Should Be Submitted within 45 Days to Maintain Review Schedule
ML19317H425
Person / Time
Site: Trojan File:Portland General Electric icon.png
Issue date: 05/14/1980
From: Clark R
Office of Nuclear Reactor Regulation
To: Goodwin C
PORTLAND GENERAL ELECTRIC CO.
References
NUDOCS 8006050536
Download: ML19317H425 (4)


Text

7 em a n.

UNITED STATES

[Ejh M NUCLEAR REGULATORY COMMISSION

~

3.*y\\ ^-

'e r

WASHINGTON, D. C. 20555 a.

\\~O+....f May 14, 1980 Docket No. 50-344 Mr. Charles Goodwin, Jr.

Assistant Vice President Portland General Electric Company 121 Sil Salmon Street Portland, Oregon 97204

Dear Mr. Goodwin:

In conducting our review of your letters of October 5,1979 and February 25, 1980 relating to adequacy of station electric distribution system voltages at Trojan Nuclear Plant, we have determined that we will need the additional information identified in the enclosure to continue our review.

In order for us to maintain our review schedule, your response is requested within 45 days of your receipt of this letter.

Please contact us if you have any questions concerning this request.

Sincerely, R. A. Clark, Chief Operating Reactors Branch #3 Division of Licensing

Enclosure:

Request for Additional Inf.]rmation cc w/ enclosure:

See next page 3006050 T N

Mr. Charles Goodwin, Jr.

Portland 3eneral Electric C'ompany cc-Mr. J. W. Durha=, Esquire Robert M. Hunt, Chairman Vice President and Corporate Counsel Board of County Comissioners Pertland General Electric Company Columbia County 121 S.W. Salcon Street St. Helens, Oregon 97501 Pertland, Oregon 97204 Warren Hastings, Esquire Counsel for Portland General Electric Cc:pany 121 S.W. Salmon Street Portland, Oregon 97204 Mr. Jack W. Lentsch, Manager Generation Licensing and Analysis Pcrtland General Electric Company 121 S.W. Salmon Street Portland, Oregon 97204 Colu=bia County Courthouse Law Library, Circuit Court Room St. Helens, Oregon 97501 Director, Oregon Department of Enargy Labor and Indstries Building, Room 111 Salem, Oregon 97310 Richard M. Sandvik, Esquire Counsel for Oregon Energy qcility Siting Counsel and Oregon Department cf Energy 500 Pacific Building 520 S.W. Yanhill

?crtland, Oregon 97204 Michael Main:rcs, Resident Inspector

'J. S. Nuclear Regulatory Ccmission Trojan Nuclear Plant P. O. Box 0 Rainier, Oregon 97048 Mr. Denald W. Godard, Supervisor Siting and Regulation

~

Oregon Departrent of Energy Labcr and Indstries Building, Room 111 Salem, Oregon 97310 G

~~~,..~

~

.~

~'

ENCLOSURE TROJAN NUCLEAR PLANT (DOCKET NO. 50-344)

REQUEST FOR ADDITIONAL INFORMATION ON ADEQUACY OF STATION ELECTRIC DISTRIBUTION SYSTEM VOLTAGES

References:

NRC generic letter to all power reactor licensees, " Adequacy of Station a.

Electric Distribution System Voltages," dated August 8, 1979.

b.

PCE (C. Goodwin, Jr.) letter to NRC, dated October 5, 1979.

PGE (C. Goodwin, Jr.) letter to NRC, dated February 25, 1980.

c.

Questions:

1.

Supply the calculated voltages for low voltage AC (less than 480 V) class 1E buses for each analyzed case. Do these systems supply any instruments and control circuits as required by GDC 137 If so, is all equipment capable of sustaining the analyzed voltages (without blowing fuses, overheating, etc.)?

Is the ccanected equipment qualified by the manufacturers to withstsnd the expected voltages without affecting their ability to perform the required function?

b 2.

Case 10 assumes a tap change (to +2.5% tap) on the start-up trans-former. Was this tap change also applied in the reference e analysis?

PGE should justify this since guidelines 4 and 11" prohibit manual actions of this type for this analysis.

D 3.

Case S shows the lowest bus voltage caused by starting a circula-tion water pump when the grid voltage is at 235 kV.

Since reference e analyzes for a 230 kV grid voltage, case 5 should be done for this lower grid voltage. Give the effect of starting and running this load 8

on all class lE buses and loads per NRC guideline 3. What are the bus and load voltages when starting the largest 480 V class IE load when all class IE loads are operating at full load?