Gentlemen:
Cg)
~
{
i
~
Inresponse.toyourrequestdatedfone 28, 1976, the Comission has issued the enclosed Amendment No.14 to facility License No. DPR-51 for the Arkansas Nuclear One - Unit No.1 facility.
This amendment revises control rod withdrawal limit curves (Figures 3.5.2-1B and 3.5.2-1C) to establish a'+ 10 effective full power day i
(EFPD) band when. switching between the two curves at 435 EFPD.
We have found that ' portion of your June 28, 1976 request involving changes in the test interval for the diesel generator test, the reactor building isolation trip test and the service water system tests unacceptable _since the requested changes could lengthen the j
surveillance interval to up to 48 mGaths. However, your response to our letter of June 7,1976 (D. L. Ziemann to J. D. Phillips), should resolve your problem with these specifications in an acceptable manner.
Copies of the related Safety. Evaluation and the Notice of Is'suance are also enclosed.
Sincerely,
~
\\
Original signed by M.Grotenhuis Dennis L. Zienann, Chief Operating Reactors Branch #2 l
. Division of Operating Peactors
Enclosures:
8 0 0 4 210 [/Q
.See next page
. NOTE: SEE PREVIOUS YELLOW FOR q NCURRENCE f
OR:0RB #2_
OR:0RB #2 OR:RSB/0T OEL gR:0RB #2,..
RMDiggs
_.ts-J~LZiemann q
/g go WEConverse:rc RBaer 8/ /76*
8/ /76
- 8/ /76*
(//a/76 _
r on>
r.- ac.n.im. 533incu.2.o
. y.........................
-. =
^
s
~
i DISTRIBUTION
~
t Docket TBAbernathy NRC PDR JRBuchanan Local PDR OPA (Clare Miles)
ORB #2 Reading ACRS(16) i V5tello Docket No. 50-313 Dross KRGoller l
TJCarter.
WEConverse Arkansas Power & Light Company RDSilver ATTN: Mr. J. D. Phillips-RMDiggs Senior Vice President 0 ELD Production Transmission and OI&E(5) i Engineering ~
bo~nes(4)
Sixth and Pine Streets BScharf (10)
Pine Bluff, Arkansas 71601-JMcGough Gentlemen-
~
)
In response.to your request dated June 28,1976, the C' omission has issued the enclosed Amenhent No.14 to Facility License No. DPR-51 for the Arkansas Nuclear One - Unit No.1 facility.
This amendment (1) revises control rod withdrawal limit curves (Figures 3.5.2-1B and 3.5.2-1C) to establish a + 10 effective full power day (EFPD) band when switching between the two curves at 435 EFPD and (2) changes the frequency of the Reactor Building Isolation Trip test, the Service Water System functional test and certain diesel generator operability tests to "once per refueling period" vice "each refueling outage." or "once each refueling shutdown."
Copies of the related Safety Evaluation and the Notice of Issuance are also enclosed.
Sincerely, Dennis L. Ziemann, Chief Operating Reactors Branch #2 j
Division of Operating Reactors i
i
Enclosures:
1.
Amendment No.14 to '
L License No. DPR-51 2.
Safety Evaluation.
3.
Notice l
~
-f OR:RSBk0j B#2[~
OR:
0R:0RB #2 OR:PSB/0T-OELD OR:0RB #2 o,,ic.,
RM l
j%hbdBaer WButler DLZiemann om,
'8/d/76 8/6/76 8/ /76.
8/ /76 8/ /W
/
76 Forms AIC 318 (Rev. 9-53) ABCM 0240-
- u. s. eovsnmuswr raintime orrects sera.ese.coe m.~n:-
.r.
~
n.
.. e :.-
Arkans'as Power & Light Company 2
September 10, 1976
Enclosures:
1.
Amendment No.14 to License No. OPR-51 2.
Safety Evaluation 3.
Notice cc w/ enclosures:
Horace Jewell, Escuire House, Holms & Jewell 1550 Tower Building Little Rock, Arkansas 72201 Mr. Donald Rueter Manager, Licensing Arkansas Power & Light Company Post Office Box 551 Little Rock, Arkansas 72201 Arkansas Polytechnic College Russellville, Arkansas 72801 Honorable Ermil Grant Acting County Judge of Pope County Pope County Courthouse Russellville, Arkansas 72801 cc w/ enclosures and cy of AP&L filing dtd. 6/28/76: