ML19317G912

From kanterella
Jump to navigation Jump to search
Requests Review of Flooding Potential of Equipment in Fire Protection & Circulating Water Sys.Response Due within 30 Days
ML19317G912
Person / Time
Site: Quad Cities, Rancho Seco  Constellation icon.png
Issue date: 09/26/1972
From: Deyoung R
US ATOMIC ENERGY COMMISSION (AEC)
To: Davis E
SACRAMENTO MUNICIPAL UTILITY DISTRICT
References
NUDOCS 8004020569
Download: ML19317G912 (2)


Text

_.. -

  1. d Docket tio. 50-312 Sacranento Municipal Utility District ATTII:

Mr. E. K. Davis, General Counsel 620A 3 Street, P.O. Box 15830 Sacramento, California 95313 Gentlemen:

A failure of an expansion bellous in ene circulatin; water line which serves the main condenser recently occurred at Quad-Cities, Unit 1.

The resultant flooding caused degradation of sono safety-related equipment.

You are requested to review Ih.ncho Seco Muclear Generatint; Station to determine whether the failure of any non-Category I (seismic) equipment, particularly in the circulating water systen and fire protection system, could renuit in a condition, such as flooding or the release of cherticals, that rtight potentially adversely affect the performance of safety-related equipment required for safe shutdoun of the facility or to limit the consequences of an accident.

Tac integrity of barriors to protect critical equipment from potentially damaging canditions should be assuued only when the barrier has been specifically desi;:ned for such conditions.

If your revica deternines that safety-related equipment could be adversely affected, provide your plans and schedules for corrective action.

Please submit your response uitnin 30 days of reccipt of this letter.

Sincerely, Oricinal signed by R. C. DeYaunz; R. C. De'ioung, Assistant Director for Pressurized Water Ecactors Directorate of Licensing,

.c :

See next parc omCE >

$URNAME>

CATE >

? u s sa.t -ww p.-

.va<t M71 -44r. -15 4 Ferm AEC-H 6 t Res. 9-Sii AECM 0240 seo4o2o56y e

Sacramento Municipal Utility District SEP

e. G 1972 cc: Mr. David S. Kaplan, Secretary and Attornay 6201 s Straat P.O. Box 15830 Sacramento, California 95813 DISTRIBUTION:

Docket AEC PDR Local PDR RP Reading PWR-4 Reading RCDeYoung RBoyd PWR Branch Chiefs EH OGC RWKlecker EIGoulbourne (2)

BBuckley 1

i or icc. [. PVR,4..

P }/ 4

...AD :Py/,.

,, [.

t>Co i

.......... ' ve n ce r RCDeYdtmg i

BBuckley:ttb AS 1VRN&ME *,.............

l 9/ /72

,,<......j...., f, _

g 9/c /72 Y

9/'X772 DATE>*

7 AEC 319 iRei. 4.5P AECM 0240