ML19317G045

From kanterella
Jump to navigation Jump to search
Notice of Deviation from Insp on 791108-10,15-18 & 1201-02
ML19317G045
Person / Time
Site: Rancho Seco
Issue date: 12/22/1976
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
To:
Shared Package
ML19317G025 List:
References
50-312-76-09, 50-312-76-9, NUDOCS 8002210746
Download: ML19317G045 (1)


Text

'

G l

l Appendix B t

Notice of Deviation Sacramento Municipal Utility District Sacramento, California Docket No. 50-312 Based on the results of an NRC inspection conducted on November 8-10, 15-18 and December 1-2, 1976 it appears that one of your activities deviated from generally accepted industry practices as indicated below:

A.

Contrary to ANSI N13.1-1969, " Guide to Sampling Airborne Radio-active Materials in Nuclear Facilities," at the time of the in-spection the sampling system for the gland steam condenser exhaust had several mechanisms installed upstream of the collection media which precluded the collection of a representative sample of iodine and particulates.

O i

U 8002 210 %g d

L j