ML19317F019

From kanterella
Jump to navigation Jump to search
AO-287/74-08:on 741114,reactor Protective Sys Bistable Failed Following Flux Trip Setpoint Change.Cause Not Stated.High Flux Bistable Replaced & Proper Operation Verified
ML19317F019
Person / Time
Site: Oconee 
Issue date: 11/29/1974
From:
DUKE POWER CO.
To:
Shared Package
ML19317E999 List:
References
NUDOCS 8001080723
Download: ML19317F019 (1)


Text

- _ -

g, n

Duke Power Company Oconee Unit 3.

Report No: A0-287/74-8 Report Date:

November 29, 1974 Occurrence Date:

November 14, 1974 Facility: Oconee Unit 3, Seneca, South Carolina Id ntification of Occurrence:

Recctor Protective System Bistable Failure Conditions Prior to Occurrence: Unit at 40 percent full power.

Description of Occurrence:

On November 14, 1974 the Reactor Protective System (RPS) high flux trip set-point was changed from 50 percent to 80 percent full power prior to continuation of startup testing of 75 percent full power level.

It was found that the channel B high flux bistable would not trip after the new setpoint was set.

The three redundant channel high flux bistables reset properly.

The bistable was replaced and proper operation verified.

Designation of Apparent Cause of Occurrence:

The bistable has a setpoint capability of 0 to 25 percent full power (0-10 volts DC).

The setpoint of 80% corresponded to a trip voltage of 6.4 volts, however, the bistable would not trip even when the test voltage was increased to 10 volts.

This F1 stable had been successfully tested on November 7, 1974 during the online channel calibration and functional test.

This is the first failure of this type conponent among the 135 bistables utilized at the Oconee Nuclear Station.

Analysis of Occurrence:

The failure of the high flux bistable would have only prevented a channel B Reactor Protective System (RPS) trip.

This would not have affected the other three channels of the RPS. A reactor trip would have occurred, if necessary, with trip signalc from two out of the three remaining channels.

The health and safety of the public was not affected.

Corrective Action:

The high flux bistable was replaced and the proper operation verified.

Failure Data:

Bailey Company part number 6621 500 A 1.

Q 'W

& A Y

-,y 8001080 7 2 3