ML19316A201

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 780328-31
ML19316A201
Person / Time
Site: Oconee  Duke Energy icon.png
Issue date: 04/17/1978
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19316A196 List:
References
50-269-78-07, 50-269-78-7, 50-287-78-07, 50-287-78-7, NUDOCS 7911280733
Download: ML19316A201 (2)


Text

_

.p

-l 0 APPENDIX A

~

1 NOTICE OF VIOLATION Duke Power Company License Nos. DPR-38 DPR-47 DPR-55 Based on the results of the NRC inspection conducted on March 28-31, 1978, it appears that certain of your activities were not conducted in full compliance with NRC requirements as indicated below.

This item has been categoriied as described in our correspondence to you dated Dece=ber 31, 1974.

10 CFR 20.203(b') requires that each radiation area be conspicuously posted with a sign or signs bearing the radiation caution symbol and the words:

CAUTION, RADIATION AREA.

Contrary to the above, the gate to Unit 3 Waste Gas Compresso'r Room (Room 258), although posted with a radiation area sign, was observed

~

open on Furch 28, 1978, such that the sign was not conspicuous.

The room was a radiation area with a maximum radiation level of 30 crem/hr.

__This.is an infraction..

27.~._.

. L.. ' Z ~.. ~... _~J. _ T. '~ " - ~ '~ ~~ Z ~~ ' __~

B o733

,,.u a s

n-s I

(

I' APPENDIX B NOTICE OF DEVIATION e

Duke Power Company License Nos. DPR-38 DPR-47 DPR-55 Based on the results of the NRC inspection conducted on Parch 28-31, 1978, certain of your activities appear to deviate fro = y..: commitments to the Commission as indicated below.

Duke Power Company's letter to the Director, Office of Inspection and Enforcement, U. S. Nuclear Regulatory Commission, dated June 24, 1977, discussed actions to be taken in the event a primary to secondary leak is identified, and stated, in part, that the oil collection basin is initially sampled every two hours and analyzed for tritium and gamma isotopes.

Contrary to the above, subsequent to indication of primary to secondary leakage on Unit 2 on September 27, 1977, the oil collection basin was not sampled every two hours on Septe=ber 27 or September 28, even though sampling of the turbine building sump detected radioactivity during this period.

Intervals between _,__,___ _

sampling on September 27 and September 26 ranged from 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> and -

- - - ~ - -

2--------

14 minutes to 11 hours1.273148e-4 days <br />0.00306 hours <br />1.818783e-5 weeks <br />4.1855e-6 months <br /> and 29 minutes.

This is a deviation.

empsp

)

.g

.