Amend 18 to License NPF-4,correcting Administrative Error Presently Existing in Tech Specs Re Max Response Time Expected from Onset of Detected Degraded Offsite Power Sys
ML19312E785
Person / Time
Site: North Anna 
Issue date: 05/19/1980
From: Clark R
Office of Nuclear Reactor Regulation
To:
Shared Package
ML19312E786 List:
References
NUDOCS 8006090529
Download: ML19312E785 (5)


Text

- - - - _ _.

O p *'f:.a UNITED STATES

[ 4..- y; ;

NUCLEAR REGULATORY COMMISSION

,Cf E

WASHWG TON, D. C. 20555

( N M,[

VIRGINIA ELECTRIC AND POWER COMPANY

_ DOCKET NO. 50-338 NORTH ANNA POWER STATION, UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.18 License No. NPF-4 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by the Virginia Electric and Power Comany (the licensee) dated January 8,1980 complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Comission's rules and regulations set forth in 10 CFR Chapter I; 5.

The facility will operate in conformity with the appli-cation, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

80060905.ti f

2_

2.

Accordingly, the license is amended by changes to the Technical Szecifications as indicated in the attachment to this license amendment, and paragraph 2.0.(2) of Facility Operating License No. NPF-4 is hereby amended to read as follows:

2.0.(2) Technical Soecifications The Technical Specifications contained in Appendices A and 3, as revised through Amendment No.18, are hereby incorporated in the license. The licensee shall operate the f acility in accordance with the Technical Specificatiens.

3.

The license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION c.

I h-Robert A. Clark, Chief Operating Reactors Branch #3 Division of Licensing

Attachment:

Chan5es to the Technical Specifications Date of Issuance: May 19,1980

i ATTACHMENT TO LICENSE AMEN MENT NO. 18 FACILITY OPERATING LICEMSE NO. NPF-4 00CKET NO. 50-338 Change the following page of the Appendix "A" Technical Specifications with the enclosed page as indicated. The revised page is identified by Amendment number and contains vertical lines indicating the area of cnange.

Pace 3/4 3-29a 1

l f

i

TABLE 3.3-5 (Continued)

ENGINEERED SAFETY FEATURES RESPONSE TIfiES INITIATING SIGNAL AND FUNCTION RESPONSE TIME I!! SECONDS 6.

Steam Flow in Two S*eam Lines-High Coincident witn Steam Line Pressure-Low a.

Safety Injection (ECCS) 1 13.0#/23.0##

b.

Reactor Trip (from SI) 1 3.0 c.

Feedwater Isolation 1 8.0 d.

Containment Isolation-Phase "A" 1 18.0#/28.0##

e.

Auxiliary Feedwater Pumps 1 60.0 f.

Essential Service Water System flot Applicable g.

Steam Line Isolation 1 8.0 7.

Containment Pressure--High-High a.

Containment Quench Spray 1 60.0 b.

Containment Isolation-Phase "B" 1 60.0 8.

Containment Pressure-Intermediate Hign-High a.

Steam Line Isolation 5 7.0 9.

Steam Generator Water Level Low-Low a.

Auxiliary Feedwater Pumps 1 60.0 10.

Station Blackou*

a.

Auxiliary Feedwater Pumps Not Applicable

11. f-tain Feedwa ter Pumo Trio a.

Auxiliary Feedwater Pumos Not Applicable 12.

Steam Generator Water Level--High High a.

Turbine Trip - Reactor Trip 1 2.5 5.

Feedwater Isolation 5 11.0 NORTH ANNA - UNIT 1 3/4 3-29