T
-,1
)
l Telephone 617 366-9011 Twx 7a0 390 0739 YANKEE ATOMIC ELECTRIC COMPANY n.3.2.1 WYR 80-35 J&lh 20 Turnpike Road Westborough, Massachusetts 01.581
- YAN KEE March 17, 1980 United States Nuclear Regulatory Commission Washington, D. C.
20555 Attention':
Office of Nuclear Reactor Regulation Mr. Darrell G. Eisenhut, Acting Director
Reference:
(1 ) License No. DPR-3 (Docket No. 50-29)
(2) USNRC Letter to YAEC dated February 23, 1980
Subject:
LWR Primary Coolant System Pressure Isolation Valves
Dear Sir:
Reference (2) requested that we review the Low Pressure Safety Injection System and any other system which might have a valve configuration which.could lead to an Event V accident. The valve configurations which might lead to this event are two check valves in series, or two check valves in series with a motor operated valve.
The valve configuration of the low pressure and high pressure portions of the Safety Injection System are shown on attached drawing M-7.
Both portions have two safety class 1 check valves in series with a safety class 2 check valve, thereby providing three check valves in series which is not. an Event V arrangement.
Based on the above, Yankee Atomic Electric Company concludes that the Event V valve configuration does not exist at Yankee Rowe and further action is not required.
We trust that this 'information is acceptable to you; however, shoul d you have any questions, please contact us.
Very truly yours, i
ATOMIC ELECTRIC COMPANY WWW L. H. Heider Vice President COMMONWEALTH OF MASSACHUSETTS)
)ss-COUNTY ~OF WORCESTER
)
~
- Then personally appeared before me, L. H. Heider, who, being duly sworn,
..did state that he is a Vice President of Yankee Atomic Electric Company, that i
he is duly authorized to execute and file the foregoing request in the name and on the behal f of Yankee Atomic Electric Company, and,wt the statements therein are true to the best of his.knowl edge and belief.
003240 $ C Robert H. Groce Notary Pub 1 ic