I-LA

+

- - < - - - +

4 O.

s ooss 0o4710 SURVEILLANCE REQUIRDIENTS Auxiliary Feedvater System The testing every three months and after cold shutdowns of the auxiliary feedvater pumps vill verify their operability by recirculating vater to the emergency feedvater storage tank and operating, cne at a time, the regulating valves 1

(HCV-11073 and ECV-11033) to confirm a flev path to the steam generators and epche.bility of the valves.

Proper functioning of the steam turbine admission valve and d

starting of the feedvater pump vill demonstrate the inte-i grity of the steam driven pump. Verificatien of correct operation vill be =ade both from instrumentation within the main centrol reem and direct visual observation of the pumps.

References I

(1)

FSAR, Sectica 9.h (2)

Technical Specification 2.5 i

l 1

l i

I e

3-62a

-. - - ~.

- ~ -..

.