n U '
'JCENSEE EVENT REPORT
- . ~
CcNrRot SLcCx:l l
l l l
l l
ptrass Paint att ascuinen inconmaTion) 1 6
LEENSEE UCENSE EVENT -
NAME LCENSE NUMBER TYPE TYPE l Cl A l R l S l Sl 1l l0 l0 l-l 0l 0l 0l 0l0 l-l0 l 0 l l4l1l1l1l1l l0 l1 l 7 89 14 15 25 26 30 31 32 CATEGORY TYP CoCKET NUMBER EVENT CATE REPORT CATE a t con'T lM l I l W
[L l l0 l 5 l 0 l-l 0 l 3 l 1l 2l l1 l0 l2 l 8 [ 7 l 7l l 1l 1l 2l 3 l 7 l 7 l 7 8 57 58 59 60 61 68 69 5
74 75 80 EVENT DESCRIPTION Eg l An inspection of the reactor building following the refueling outage on October 28 l
7 89 20 J Mlil l revealed that there were 705 pounds of uncoated aluminum in the l 3 7 89 SO EE lbu11 dine. The W reneration safety analysis assumed 500 pounds oresent for post-LOCA l 7 89 ea -
$ l vnvHan wh %cn Uvn, N 91dr 7 89 snrnv3.
A0-74-14 det:rfied a nrevious occurrence of l 5 80 HE lthis tvoe.
(RO-77-15) l 7 89 90,,
,mg 4
CE COMPONENT CODE TupER VCLATON o
l Sl El W l Z l Z l Zl Zl Zl 4 lZ]
l Zl 9l 9l 9l g
7 89 10 11 12 17 43 44 47 48 g
CAUSE DESCRIPTION
' '/
g l Inadequate controls at initial startup permitted operation without proper concern for l,
Alq l aluminum inventory. An initial attempt to establish the actual inventory omitted e0..*
7 89 l
7 89 30 to l several components.
j';;
FACE.lTY METHCo 0F STATUS
% POWER OTHER STATUS OtSCOVEPY DISCOVERY DESCRIPTON 8
LEJ l1l0l0j l NA l
[Bj l
NA l
10
_12 13 44 45 46 80 7 8 9
ACTMTY CCNTENT RELEASED CF EELEASE AMOUNT OF ACTMTY LOCATCN OF RELEASE f
tZJ LZj i
NA l
l NA i
l i
7 8 9
10 11 44 45 80 PERSONNEL EXPCSURES NUMBER TYPE DESCRIPTON 1
l 01 0l 0 l {
l NA l
7 89 11 12 13 30 PERSONNEL INJURIES NUMBER CESCR:PTON I
n r ts f
'M 7
89' 11 12 80 OTFSITE CONSEGUENCES L
E l Minitaal to none l
7 89 20 LOSS OR DAMAGE TO FAC'UTY 80OS260 h((
l
~
[ll l
NA 7 89 10 80 PUBUCITY l Local newsonners and wire services notified November 12' 1977.
]
1 7 89 oo AOCITIONat FACTCAS l The 500 pounds assu=ed in the analysis is not a limiting factor. Tne analysis will e9 30 99 j'be revised to determine the actual limit based on the Final ECCS Acceptance Criteria. l 7 89 80 R. U. M od o M. I. Usenhu d (916) 452-3211 NAME:
pHcn!;
GPO $st.ct?
4