ML19308D209

From kanterella
Jump to navigation Jump to search
Forwards RO-77-15
ML19308D209
Person / Time
Site: Crystal River 
Issue date: 02/28/1977
From: Stewart W
FLORIDA POWER CORP.
To: Moseley N
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
Shared Package
ML19308D210 List:
References
CS-77-38, NUDOCS 8002270672
Download: ML19308D209 (1)


Text

__________

~. --..

YS l

.,...e

46#

MQM8 J

g W/

i hh

\\s

'\\

power x

=

CQ a po m a Tso m 28 February 1977 3-0-3-a-1 CS-77-38 Mr. Norman C. Moseley, Director Docket No. 50-302 Office of Inspection and Enforcement License #DPR-72 U. S. Nuclear Regulatory Comission Licensee Event Report 77-15 230 Peachtree St., N.W., Suite 818 Atlanta, GA 30303

Dear Mr. Moseley:

This report is submitted in accordance with Technical Specification 6.9.1 and Regulatory Guide 1.16, Revision 4, Section C.2.b.(1) as a written Thirty (30) Day Report.

O, Technical Specification 3.7.1.3 requires that the condensate storage tank be maintained at the 150,000 gallon levei or greater. During initial filling of feedwater heaters and lines during power operation, daily surveillance showed the condensate storage tank level to be lowering below the 150,000 gallon level. The tank was filled to greater than 150,000 gallons in less than one hour.

As required by the Tech. Spec., the hotwell was monitored, and it contained greater than 200,000 gallons (150,000 gallons required).

No safety implications were presented by this occurrence.

Very truly yours, FLORIDA POWER CORPORATION L e F h u.u e_ t [

W. P. Stewart Director, Power Production WPS/jod 2/13 Enclosure 8002270 {9 %

General Office 3201 Th:fty fourtn Street south e P O Box 14042. St. Peterscurg, Fionca 33733 813-856-5151

_