eso e*

IE FrrR mPYJ M

7 February 1977

-~

g CS-77-21

' g "

  • ca.......o-3-0-3-a-1
f. 2E.S

\\-Q; @T;l;lv

!!r. Norman C. ?!oseley, Director Crystal River Unit 3 -

Office of Inspection and Enforcement Docket No. 50-302 U. S. Nuclear Regulatory Commission License #DPR-72 230 Peachtree St., N.W., Suite 818 Licensee Event Report 77-6 Atlanta, Georgia 30303

Dear lir. Moseley:

This report is submitted in accordance with Technical Specification 6.9.1 and Regulatory Guide 1.16, Revision 4, Section 2.a.(3), as a written Fourteen (14) Day Report. Your office was notified on 31 January 1977 of this event.

7-A through wall crack was found in an eight inch Schedule 40 304 stainless steel building spray pipe. This crack is in the heat affected zone of a pipeto-pipe weld at a location which may have contained stagnant water. This is the second occurrence of this Q

condition.

It was discovered coincident with our ongoing study which is being conducted in accordance with IE Circular 76-06.

A summary report will be submitted by 10 March 1977.

Very truly yours, FLORIDA POWER CORPORATION bC bAldLL.

s.

W.P. Stewart Director, Power Production DUP /ib Enc.

Nucicar Plant Ifanager j