ML19308A500

From kanterella
Jump to navigation Jump to search
Abnormal Occurrence 50-289/74-08:on 740531,during Routine Surveillance,Two Barton Instruments Found to Have Drifted. Caused by Set Point Drift.Barton Switch Recalibr & Preventive Device Installed
ML19308A500
Person / Time
Site: Crane 
Issue date: 06/03/1974
From:
METROPOLITAN EDISON CO.
To:
Shared Package
ML19308A499 List:
References
NUDOCS 7910250700
Download: ML19308A500 (2)


Text

{{#Wiki_filter:_ _ _ _.. O O .c, s.

  • s.

J - l-1 .4 .w,$ ! Pk.w.)<e r _N'1 ..: ABNORMAL OCC1)RRENCE REPORT . i j 1. Report No. '50.-220/74-8 t2a. .Date .../ June.3,~1974 2b. Occurrence Date iMay 31, 197,4 .c .3. Facility .Nine Hile Point Nuclear Station Unit 1 /4. Ident'ification of Occurrence DhQO 5etpcint drift on Drywell High Pressure hgg M b;b 3 T ' S.

Conditions Prior to Occurrence k~Y

\\ "\\

Unit.1 was shutdown for annual refueling 26.

Descriptien of Occurrence During routine surveillance testing en May 31., Ic74 at approximately 1600 hours, two Barton Instru:ents used in the trywell High Pressure -(3.5 psig) RPS were found to ha' e drifted.'20 'ssi. higher than required. v 'The surveillance test consists of operating the switch thru regulated '(tercury cancreter) air signal to 'the sensor. The two Barten Instruments >Hodel 289,.E.P. 8RE04A4D are in separato RPS trip systems.

With reactor in refuol mode and the drywell under atmospheric conditions v

no operator action was necessary, as the plant was in a safe condition. 7. ' Designation of Accarent Cause of the Occurrence Setpvint. drift c.

8.
Analysis of occurrence

'The high drywell pressure trip requires a ono.out of two twice logic to. actuate the protective function. One channel in each trip systen 'would havo actuated at the required setpoint and thus produced the . protective function. Therefore,.no hazard would have been presented l to the general public or station had the protective function been l srequired. .9. . Corrective Action The im=ediato co rective action involved recalibration of the Barton . switch. The normal valvo of setpoint is 3.S +.053 psig. A modif-ication has been made to the Barton switch. I'new switch plate lacking device to prevent setpoint drift has been installed. (AOR 74-1). This modification should reduce setpoint drift problems with this switch. i l 7910250 7 0 0

,i ...c r .aw,r.y.f. ' o.: 'J( .i d.* VN.;;,. 3,,,

A

'~ ..*:. :l .s. n. . q 6 ... s, ....n. ,Abnorcal;0ccurrence Report ', :,.I.W'- 4;2- _,..kh'une3,1974 ~ ~ J ni'.. ..n u.m ~., - ~. , ;.. a. ...}e I., ,.3,.'. .;g.].;, t '.:.,,. $ ' ,e e W ;, , i

q.... ;.

..n: 10. - Fallure Data ..w ...~ '. iNo previous setpoint drifting has cccurred on these switches this .Eyear. AOR 74 '1 concerning a Barten switch setpoint drift is the only .fother drift in setpoint taidate.in 1974. .r. ..e., '..G:,:, 1} - ~ W_ ,y.og

s

- 1.5A.i 'i ,...',"..s?.., ,0;.

  • :,. d... . Q,

y ..,..v i* .I r .D. ~ . c.j. *

  • 1. e.,

.g s, .-{.g,.. f[ ~ * ~ g ,:). 's. s i.'...= ? i ' >.e ,u., s -s e .c. <e .t. %,e " i + 3. -.c "{ . :s e ' r .-t i i 3., ( t ..-a. ,l: 'l c, e t I .1 t a.:; y,. ..s. a i e ~ 'c n t ....,. ~ g i. 4 - 4

c..,'

f l .n. t .t... ) s. t 1 a 1 i t t, f. s l .t- .t t g e f.- . I'Y ' 't. e

s. e ts d'*

t s e l c -.}}