bec to DAC:ADM:

!(pa rs%

CENTRAL FILES o,

UNITED STATES POR:HQ i

NUCLEAR REGULATORY COMMISSION LPOR 5 ','

It

[NSIC REGICN IV t

g,8 611 RYAN Pt.AZA oRIVE, SulTE tooo

%, ' **- +#

ARl.!NGTON, TEXAS 76012 States February 8, 1980

Docket Nos.

50-313 50-368 Arkansas Power and Light Company ATTN: Mr. tJilliam Cavanaugh III Vice President of Generation and Construction P. O. Box 551 Little Rock, Arkansas 72203 Gentlemen:

The enclosed IE Information Notice is forwarded to you for information.

No written response to this Information Notice is required.

If you have any questions related to the subject, please contact this office.

Sincerely, e

0

% L]nb J(

K. 7. Seyfri' Director

Enclosures:

1.

II Information Notice No. 80-05 2.

List of Racently Issued IE Information Notices cc:

James P. O'Hanlon, Plant Mant. n-Arkansas Nuclear One

?. O. 3ox 608 Russellville, Arkansas 72801 8003250598

SSINS No.:

6870 Accession No.:

UNIT *.D STATES 7912190673 NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 IE Information Notice No. 80-05 Date: February 8,1980 Page 1 of I e

CHLORIDE CONTAMINATION OF SAFETY RELATED PIPING AND COMPONENTS A Bechtel Power Corporation Study at the Wolf Creek Project has revealed that a fire retardent coating is potentially corrosive in contact with stainless steel.

I Albi "Duraspray" is a fire retardent coating which contains magnesium oxychloride, and is used for fireproofing of exposed structural steel in some Nuclear Power Plants. There appears to be no deleterious effect when it is applied over unprimed, inorganic zine coated, or galvanized steel, however, it may be corrosive in contact with stainless steel, bare aluminum or copper.

Droppings or overspray of this material cannot be properly removed with water.

Diluted Nitric acid has been proven to be a useful cleanser, however, it presents a safety hazard.

Applicants and holders of construction permits and licensees of operating power _ reactors are advised to protect all stainless steel, copper and aluminum material from overspray and droppage of cementitious oxychloride materials and to remove accidently applied materials immediately and completely employing strict safety precautions during the process.

Special attention should be given i

to weld areas in any removal procedures.

No written response to this information notice is required.

If you require additional information regarding this matter contact the Director of the appropriate NRC Regional Office.

l l

i I

IE Information Notice No. 80-05 February 8, 1980 LISTING OF RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Date Issued To Notice No.

Issued 79-34 Inadequate Design of 12/27/79 All holders of of Safety-Related Heat power reactor Exchangers Operating Licenses (OLs) and Con-struction Permits (cps) 79-35 Control of Maintenance 12/31/79 All power reactor facilities and Essential Equipment with an Operating Licenses (OLs) and Construction Permits (cps) 79-36 Computer Code Defect 12/31/79 All holders of power reactor Stress Analysis of Piping Operating Licenses (OLs)

Elbow and Construction Permits (cps) 79-37 Jracking in Low Pressure 12/28/79 All holders of power reactor Turbine Discs Operating Licenses (OLs) and Construction Permits (cps) 80-01 Fuel Handling Events 1/4/80 All holders of power reactor Operating Licenses (OLs) and Construction Permits (cps) 80-02 8X8R Water Rod Lower 1/25/80 All BWR Facilities End Plug Wear holder of power reactor Operating Licenses (OLs) or Construction Permits (cps)

.80-03 Main Turbine Electro-1/31/80 All holders of power Hydraulic Control System reactor Operating Licenses (OLs) and Construction Permits (cps) 80-04 BWR Fuel Exposure in

.2/4/80 All BWR's holding a Excess of Limits power reactor Operating License (OL) or Construction Permit (CP)

Enclosure