ML19305B946
| ML19305B946 | |
| Person / Time | |
|---|---|
| Site: | Bailly |
| Issue date: | 03/14/1980 |
| From: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| To: | Shorb E NORTHERN INDIANA PUBLIC SERVICE CO. |
| References | |
| NUDOCS 8003250377 | |
| Download: ML19305B946 (1) | |
Text
-
s nf n,rin n A L, j 0, w % u. w
~
hAd 14 W Docket No. 50-367 Nortnern Indiana Public Service Company ATTN:
Mr. Eugene M. Shorb Senior Vice President 5265 Hohman Avenue Hammond, IN 46325 Gentlemen:
This Information Notice is provided as an early notification of a possibly significant matter.
It is expected that recipients will review the infor-mation for possible applicability to their facilities. No specific action or response is requested at this time.
If further NRC evaluations so in-dicate, an IE Circular, Bulletin, or Generic Letter will be issued to recommend or request specific licensee actions.
If you have any questions regarding this matter, please contact the Director of the appropriate NRC Regional Office.
Sincerely, James G. Kepple.
Director
Enclosure:
IE Information Notice No. 80-11 cc w/ encl:
Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR NSIC TIC Mr. Dean Hansell, Of fice of Assistant Attorney General RIII RIII fhV Y
Fior li/km N:ppler 3/14/80 8003 250 3 77Q
/.
5..
SSINS No. 6870 Accession No.:
UNITED STATES 7912190684 NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 pe March 14, 1980 IE Information Notice No. 80-11 GENERIC PROBLEMS WITH ASCO VALVES IN NUCI
'PLICATIONS INCLUDING FIRE PROTECTION SYSTEMS Description of Circumstances: is a Recall Notice from The Viking Corporation, dated July 16, 1979 that identifies ASCO valves used in certain Viking fire protection equipment that could fail.
Licensees should review their fire protection system components to determine if the equipment identified in the Viking Recall Notice is in their facility.
If the identified equipment is installed in the fire protection system, then the modifications specified in the Recall Notice should be made and tested for proper operation.
The requirements of the technical specifications or any other licensee commitment should be complied with when a fire protection
~ystem is disabled.
South Carolina Electric and Gas Company (Virgil C. Summer Nuclear Station) reported to the NRC on October 24, 1979, a potential significant deficiency regarding the effects of oil on elastomeric miterials used in ASCO NP-1 solenoid valves.
Specifically,'these valves utilize an ethylene propylene elastomer which expands or swells when brought into contact with oils, possibly causing valve failure.
For this reason, ASCO specifies these NP-1 solenoid valves for use in " oil free instrument air" systems.
Although instrument air syste: 5 are " oil free'.' by design, installation instructions may specify the u te of thread lubricants utilizing an oil base.
Thus, the potential exists for traces of this lubricant from threaded connec-tions in the air system, in addition to traces of oil from the air compressors themselves, to come into contact with the elastomers in the solenoid valves.
Degraded elastomers can cause the solenoid valve to fail by sticking, swelling closed flow paths, or rupturing causing leakage across the seat or to atmosphere.
Failure of the solenoid to function properly on an active valve could prevent a system from performing its required safety function.
Some ASCO NP-1 solenoid valves are equipped with tags which state:
"Important -
this valve is equipped with ethylene propylere elastomers which can be attacked by oils and greases. To be used for oil-free instrument quality air.
Clean pipe threads of cutting oils." Care should be taken to use approved thread lubricants which do not contain oil for the installation of these valves.
i I
I IE Information Notice No. 80-11 March 14, 1980 Page 2 of 2 ASCO offers viton clastomers as an option for their.hT,1 solenoid valves. The viton elastomers are not affected by oil or grease. Replacement kits of viton elastomers are available for the NP-1 solenoid valves fron. ASCO.
It is recom-manded that ethylene propylene elastomers found in Class IE qualified ASCO l
hT-1 solenoid valves be replaced with the viton kits.
In addition, enclosed is a letter from EG&G (Enclosure 2) dated December 26, 1979 that provides the results of an LER review of failure of solenoid valves.
This Information Notice provided information about a potential safety concern.
No written response is required.
If you desire additional information regarding this matter, contact the Director of the appropriate Regional Office.
Enclosure:
1.
Vihing Corporation Recall Notice 2.
EG&G Letter, Dearien to Tiller dated December 26, 1979 I
DUPLICATE DOCUMENT I:ntire documc it previously entered into system under:
hh ANO No. of ages:
m
---