ML19305B282

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 80-05, Chloride Contamination of Safety-Related Piping & Components. No Written Response Required
ML19305B282
Person / Time
Site: Summer 
Issue date: 02/08/1980
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Nichols T
SOUTH CAROLINA ELECTRIC & GAS CO.
References
NUDOCS 8003190440
Download: ML19305B282 (1)


Text

.o acy

/

UNITED STATES A

['h, (

NUCLEAR REGULATORY COMMISSION sg

.y (%,

e REGION ll g T.g;* (i a f

101 MARIETTA ST., N.W., SU.TE 3100

...../

  1. .g

/

ATLANTA, G EoRGIA 30303 FEB 6 19 S 0 In Reply Refer To:

RII:JP0 60395)

~

South Carolina Electric and Gas Company Attn:

T. C. Nichols, Jr., Vice President Power Production and System Operations Post Office Box 764 Columbia, South Carolina 29218 Gentlemen:

The enclosed IE Information Notice is forwarded to you for information. No written response to this Information Notice is required.

If you have any questions related to the subject, please contact this office.

Sincerely,

/-

[f-' James P. O'Reilly Director

Enclosures:

1.

IE Information Notice No. 80-05 2.

List of Recently Issued IE Information Notices B

d*

k 4

p

.. -80031?o yyg -

a SSINS No.:

6870 Accession No.:

UNITED STATES 7912190673 NUCLEAR REGULATORY COMMISSION g

c, g

OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555

' eu -

m e0 s

February 8, 1980 IE Information Notice No. 80-05 CHLORIDE CONTAMINATION OF SAFETY RELATED PIPING AND COMPONENTS A Bechtel Power Corporation Study at the Wolf Creek Project has revealed that a fire retardent coating is potentially corrosive in contact with stainless steel.

Albi "Duraspray" is a fire retardent coating which contains magnesium oxychloride, and is used for fireproofing of exposed structural steel in some Nuclear Power Plants. There appears te e no deleterious effect when it is applied over unprimed, inorganic zinc e.ted, or galvanized steel, however, it may be corrosive in contact with stainless steel, bare aluminum or copper. Droppings or overspray of this material cannot be properly removed with water. Diluted Nitric acid has been proven to be a useful cleanser, however, it presents a safety hazard.

Applicants and holders of construction permits and licensees of operating power reactors are advised to protect all stainless steel, copper and aluminum material from overspray and droppage of cementitious oxychloride materials and to remove accidently applied materials immediately and completely employing strict safety precautions during the process. Special attention should be given to weld areas in any removal procedures.

No written response to this information notice is required.

If you require additional information regarding this matter contact, Director of the I,

appropriate NRC Regional Office.

~ _ - _

IE Information Notice No. 80-05 Enclosure February 8, 1980 RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Date Issued To Notice No.

Issued 80-05 Chloride Contamination of 2/8/80 All holders of power Safety Related Piping and reactor OLs and cps Components 80-04 BWR Fuel Exposure in 2/4/80 All BWR's holding a Excess of Limits power reactor OL or CP 80-03 Main Turbine Electro-1/31/80 All holders o( power Hydraulic Control System reactor OLs and cps 80-02 8X8R Water Rod Lower 1/25/80 All BWR Facilities End Plug Weir holder power reactor Ols or cps 80-01 Fuel Handling Events 1/4/80 All holders of power reactor OLs and cps 79 '7 Cracking in Low Pressure 12/28/79 All power reactor OLs Turbine Discs and cps 79-36 Computer Code Defect in 12/31/79 All power reactor OLs Stress Analysis of Piping and cps i

Elbow 79-35 Control of Maintenance 12/31/79 All power reactor facilities and Essential Equipment with an OL or CP 79-34 Inadequate Design of 12/27/79 All holders of power reactor Safety-Related Heat Exchangers OLs and cps 79-33 Improper Closure of Primary 12/21/79 All power reactor facilities Containment Access Hatches holding OLs and cps 79-32 Separation of Electrical 12/21/79 All power reactor facilities Cables for HPCI and ADS holding OLs and cps 79-31 Use of Incorrect Amplified 12/13/79 All holders of power reactor Response Spectra (ARS)

OLs and cps 79-30.

Reporting of Defects and 12/6/79 All power reactor facilities Noncompliance, 10 CFR Part 21.

holding OLs and cps and vendors inspected by LCVIP

.