'o UNITED STATES
' C 8
~,,
NUCLEAR REGULATORY COMMISSION n
S nS REGION 111
/[
Q 799 ROOSEVELT ROAD GLEN ELLYN,ILLINOls 60137 FG s seo Docket No. 50-341 The Detroit Edison Company ATTN:
Mr. Edward Hines, Assistant Vice President and Manager Quality Assurance 2000 Second Avenue Detroit, MI 48226 Gentlemen:
The enclosed IE Information Notice is forwarded to you for information.
No written response to this Information Notice is required.
If you have any questions related to the subject, please contact this office.
Sincerely, MM ames G. Kepp er Director
Enclosure:
IE Information Notice No. 80-05 cc w/ encl:
Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR NSIC TIC Ronald Callen, Michigan Public Service Comr. ssion Eugene B. Thomas, Jr.,
Attorney 8003190
t k, '
SSINS No.:
6870
%+
Accession No.:
UNITED STATES 7912190673 NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT
~~
p MP, WASHINGTON, D.C.
20555 o{ a d 5
~
a February 8, 1980 IE Information Notice No. 80-05 CHLORIDE CONTAMINATION OF SAFETY RELATED PIPING AND COMP 0NL4TS A Bechtel Power Corporation Study at the Wolf Creek Project har <evealed that a fire retardent coating is potentially corrosive in contact with stainless steel.
Albi "Duraspray" is a fire retardent coating which contains magnesium oxychloride, and is used for fireproofing of exposed structural steel in some Nuclear Power Plants.
There appears to be no deleterious effect when it is applied over unprimed, inorganic zinc coated, or galvanized steel, however, it may be corrosive in contact with stainless steel, bare aluminum or copper.
Droppings or overspray of this material cannot be properly removed with water.
Diluted Nitric acid has been proven to be a useful cleanser, however, it presents a safety hazard.
Applicants and holders of construction permits and licensees of operating power reactors are advised to protect all stainless steel, copper and aluminum material from overspray and droppage of cementitious oxychloride materials and to remove accidently applied materials immediately and completely employing strict safety precautions during the process.
Special attention should be given to weld areas in any removal procedures.
No written response to this information notice is required.
If you require additional information regarding this matter contact the Director of the appropriate NRC Regional Office.
r~-
k, w*
IE Information Notice No. 80-05 Enclosure February 8, 1980 RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Date Issued To Notice No.
Issued 80-04 BWR Fuel Exposure in 2/4/80 All BWR's holding a Excess of Limits power reactor OL or CP 80-03 Main Turbine Electro-1/31/80 All holders of power Hydraulic Control System reactor OLs and cps 80-02 8X8R Water Rod Lower 1/25/80 All BWR Facilities End Plug Wear holder power reactor OLs or cps 80-01 Fuel Handling Events 1/4/80 All holders of power reactor OLs and cps 79-37 Cracking in Low Pressure 12/28/79 All power reactor OLs Turbine Discs and cps 79-36 Computer Code Defect in 12/31/79 All power reactor OLs Stress Analysis of Piping and cps Elbow 79-35 Control of Maintenance 12/31/79 All power reactor facilities and Essential Equipnent with an OL or CP 79-34 Inadequate Design of 12/27/79 All holders of power reactor Safety-Related Heat Ols and cps Exchangers 79-33 Improper Closure of 12/21/79 All power reactor facilities Primary Containment holding OLs and cps Access Hatches 79-32 Separation of Electrical 12/21/79 All power reactor facilities Cables for HPCI and ADS holding Ols and cps 79-31 Use of Incorrect Amplified 12/13/79 All holders of power reactor Response Spectra (ARS)
Ols and cps 79-30 Reporting of Defects and' 12/6/79 All power reattor facilities Noncompliance, 10 CFR Part 21.
holding OLs and cps and vendors inspected by LCVIP 79-29 Loss 4. to qSaSety-Related 11, 16/79 All power reactor facilities R;,e tD e f 31 ant System holding OLs or cps
.m au& ' stion During C'aration