ML19296C041
| ML19296C041 | |
| Person / Time | |
|---|---|
| Site: | 05000363 |
| Issue date: | 02/08/1980 |
| From: | Grier B NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I) |
| To: | Finfrock I JERSEY CENTRAL POWER & LIGHT CO. |
| References | |
| NUDOCS 8002250110 | |
| Download: ML19296C041 (1) | |
Text
.,i..
b o,,
UNITED STATES E
NUCLEAR REGULATORY CC.'.1 MISSION g
g e
REGION i os 631 PARK AVENUE KING OF PRUSSIA, PENNSYLVANIA 19406 FEB 03 1993 Docket No. 50-363 Jersey Central Power and Light Company ATTN:
Mr. I. R. Finfrock, Jr.
Vice President 260 Cherry Hill Road Parsippany, New Jersey 07054 Gentlemen:
The enclosed IE Information Notice is forwarded to you for information. No written response to this Information Notice is required.
If you have any questions related to the subject, please contact this office.
Sincerely, Boyce H. Grier
" Director
Enclosures:
1.
IE Information Notice No. 80-05 2.
List of Recently Issued IE Information Notices CONTACT:
L. E. Tripp (215-337-5282) cc w/encls:
M. K. Pastor, Project Mangger 8002250
o ENCLOSURE 1 SSINS No.:
6870 Accession No.:
UNITED STATES 7912190673 NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 IE Information Notice No. 80-05 Date:
February 8, 1980 Page 1 of 1 CHLORIDE CONTAMINATION OF SAFETY RELATED PIPING AND COMPONENTS A Bechtel Power Corporation Study at the Wolf Creek Project has revealed that a fire retardant coating is potentially corrosive in contact with stainless steel.
Albi "Duraspray" is a fire retardant coating which contains magnesium oxychloride, and is used for fireproofing of exposed structural steel in some Nuclear Power Plants.
There appears to be no deleterious effect when it is applied over unprimed, inorganic zinc coated, or galvanized steel, however, it may be corrosive in contact with stainless steel, bare aluminum or copper.
Droppings or overspray of this material cannot be properly removed with water.
Diluted Nitric acid has been proven to be a useful cleanser, however, it presents a safety hazard.
Applicants and holders of construction permits and licensees of operating power reactors are advised to protect all stainless steel, copper and aluminum material from overspray and droppage of cementitious oxychloride materials and to remove accidently applied materials immediately and completely employing strict safety precautions during the process.
Special attention should be given to weld areas in any removal procedures.
No written response to this information notice is required.
If you require additional information regarding this matter contact the Director of the appropriate NRC Regional Office.
ENCLOSURE 2 IE Information Notice No. 80-05 Date:
February 8,1980 Page 1 of 1 RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Date Issued to Notice No.
Issued 79-29 Loss of Nonsafety Related 11/19/7S-All Power Reactor Faci-Reactor Coolant System In-lities with an Operating strumentation During Operation License (0L) or Construction Permit (CP) 79-30 Reporting of Defects and 12/6/79 All Power Reactor Faci-Noncompliances, 10 CFR lities with an OL Part 21 or CP 79-31 Use of Incorrect Amplified 12/13/79 All Power Reactor Faci-Response Spectra (ARS) lities with an OL or CP 79-32 Separation of Electrical 12/21/79 All Power Reactor Faci-Cables for HPCI and AD5 lities with an OL or CP 79-33 Improper Closure of Primary 12/21/79 All Power Reactor Faci-Containment Access Hatches lities with an OL or CP 79-34 Inadequate Design of Safety-12/31/79 All Power Reactor Faci-Related Heat Exchangers lities with an OL or CP 79-35 Control of Maintenance 12/31/79 All Power Reactor Faci-and Essential Equipment lities with an OL or CP 79-36 Computer Code Defect in 12/31/79 All Power Reactor Faci-Stress Analysis of Piping lities with an OL or CP Elbow 79-37 Cracking in Low Presssure 12/31/79 All Power Reactor Faci-Turbine Discs lities with an OL or CP 80-01 Fuel Handling Events 1/4/80 All Power Reactor Faci-lities with an OL or CP 80-02 8X8R Water Rod Lower 1/25/80 All BWR Facilities with End Plug Wear an OL or CP 80-03 Main Turbine Electro-1/31/80 All Power Reactor Faci-hydraulic Control System lities with an OL or CP 80-04 BWR Fuel Exposure in Excess 2/4/80 All BWR Facilities with of Limits an OL or CP