ML19296A474

From kanterella
Jump to navigation Jump to search
Forwards IE Bulletin 79-02,Pipe Support Base Plate Designs Using Concrete Expansion Anchor Bolts
ML19296A474
Person / Time
Site: Salem, Hope Creek  PSEG icon.png
Issue date: 03/08/1979
From: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Martin T
Public Service Enterprise Group
References
NUDOCS 7903280021
Download: ML19296A474 (1)


Text

72pA.

[jk*"80, 0

UNITED STATES NUCLEAR REGULATORY COMMISSION

f. ',, )g/

REGION 1

$ g. g 431 PARK AVENUE KING OF PR U$51 A, PENNSYLVANI A 19406 March 8, 1979 Docket Nos. 50-354 50-355 50-311 Public Service Electric & Gas Company ATTN: Mr. T. J. Martin Vice President Engineering and Construction 80 Park Place Newark, New Jersey 07101 Gentlemen:

The enclosed IE Bulletin No. 79-02 is forwarded to you for action.

A written response is required.

If you desire additional information regarding this matter, plecse contact this office.

Sincerely, PP.L

(

Boyce H. Grier Director

Enclosures:

1.

IE Bulletin No. 79-02 2.

Listing of IE Bulletins Issued in Last Twelve Mor:ths cc w/encls:

E. N. Schwalje, Manager - Quality Assurance, Engineering and Construction Denartment vsoa28 coal

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 IE Bulletin No. 79-02 Date: March 8, 1979 Page 1 of 3 PIPE SUPPORT BASE PLATE DESIGNS USING CONCRETE EXPANSION ANCHOR BOLTS Description of Circumstances:

While performing inservice inspections during a March-April 1978 refueling outage at Millstone Unit 1, structural failures of piping supports for safety equipment were observed by the licensee.

Subsequent licensee inspections of undamaged supports showed a large percentage of the concrete anchor bolts were not tightened properly.

Deficiency reports, in accordance with 10 CFR 50.55(e), filed by Long Island Lighting Company on Shoreham, indicate that design of base plates using rigid plate assumptions has resulted in underestimation of loads on some anchor bolts.

Initial investigation indicated that nearly fifty percent of the base plates could not be assumed to behave as rigid plates.

In addition, licensee inspection of anchor bolt installations at Shoreham has shown over fifty percent of the bolt installations to be deficient.

Vendor Inspection Audits by NRC at Architect Engineering firms have shown a wide range of design practices and installation procedures which have been employed for the use of concrete expansion anchors. The current trends in the industry are toward more rigorous controls and verification of the installation of the bolts.

The data available on dynamic testing of the concrete expansion anchors show fatigue failures can occur at loads substantially below the bolt static capacities due to material imperfections or notch type stress risers.

The data also show low cycle dynamic failures at loads below the bolt static capacities due to joint slippage.

Action to be Taken by Licensees and Permit Holders:

For pipe support bate plates that use concrete expansion anchor bolts in Saismic Category I systems as defined by Regulatory Guide 1.29, " Seismic Design Classification" Revision 1, dated August 1973 or as defined in the applicable FSAR.

1.

Verify that pipe support base plate flexibility was accounted for in the calculation of anchor bolt loads.

In lieu of supporting analysis justifying the assumption of rigidity, the base plates 7003140008