ML19290F081
| ML19290F081 | |
| Person / Time | |
|---|---|
| Site: | Farley |
| Issue date: | 03/07/1980 |
| From: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| To: | Clayton F ALABAMA POWER CO. |
| References | |
| NUDOCS 8003180067 | |
| Download: ML19290F081 (2) | |
Text
'o UNITED STATES NUCLEAR REGULATORY COMMISSION
),
g
. r REGION il k
f 101 MARIETTA ST N.W.. SUlTE 3100 5
g' ATLANTA, GEORGIA 30303 In Reply Refer To:
MAR 0 71980 RII:JPO C5 -34'8
Alabama Power Company Attn:
F. L. Clayton Senior Vice President Post Office Box 2641 Birmingham, AL 35291 Gentlemen:
The enclosed IE Information Notice is forwarded to you for information.
No written response to this Information Notice is required.
If you have any questions related to the subject, please contact this office.
Sincerely, r
k,1
- "=
/
James P. O'Reilly Director
Enclosures:
1.
IE Information Notice No. 80-09 2.
List of Recently Issued IE Information Notices 9
-s 3
80031 8 S67
9 Alabama Power Company,
cc w/ enc 1:
A. R. Barton Executive Vice President Post Office Box 2641 Birmingham, Alabama 35291 J. T. Young Vice President-Production Post Office Box 2641 Birmingham, Alabama 35291 C. Biddinger, Jr.
Manager-Corporate Quality Assurance Post Office Box 2641 Birmingham, Alabama 35291 H. O. Thrash Manager-Nuclear Generation Post Office Box 2641 Birmingham, Alabama 35291 H. G. Hairston, III Plant Manager Drawer 470 Ashford, Alabama 36312 R. E. Hollands, Jr.
QA Supervisor Post Office Box U Ashford, Alabama 36312 J
+
i O
4
.1
.s s
3
SSINS:
6870 Accession No.
UNITED STATES 7912190681 NUCLEAR REGU1 ATOPY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.
20555 3
r 1(g r,
I March 7, 1980 U~,,
4 IE Information Notice No. 80-09 POSSIBLE OCCUPATIONAL HEALTH HAZARD ASSOCIATED WITH CLOSED COOLING SYSTEMS FOR OPERATING POWER PLANTS As a result of information that the causative agent for meningoencephalitis, the amoeba Naeglaria fowleri, had been found in warm water ponds in Florida and Texas where two fatalities were reported, NRC initiated a study by Oak Ridge National Laboratory on the occurrence of Naeglaria in power plantz with closed cycle cooling systems. For seven power stations examined (6 fossil, 1 nuclear), this study confirmed the presence of pathogenic Naeglaria at three plants including the nuclear plant (Dresden).
Recently, Northern States Power Company (NSP), while monitoring the Prairie Island Nuclear Generating Plant closed cooling system for the amoeba, did identify the presence of Naeglaria.
Although the Minnesota Department of Health does not consider the existence of the organism to be a public health threat, it was recognized as a possible occupational health hazard.
Plant personnel were instructed to wear rubber gloves when coming into contact with the circulating water and to wear respirators when working in the area of the cooling towers.
In November 1979, NSP conducted a special chlorination program at Prairie Island that was designed by Dr. Richard Tyndall of Oak Ridge to eradicate this organism.
Chlorine concentrations in the circulating water system was raised to 2.0 mg/l (measured as free chlorine) for a period of six hours to destroy both the amoebae and its encysted form.
This program also included dechlorination prior to discharge and intensive monitoring to document chlorine concentrations, the impacts of chlorinated cooling tower draf t and sampling to determine the efficacy of the special chlorination program in destroying Naeglaria.
Prelimidary results indicate that the program was successful in reducing the number of organisms present by two to three orders of magnitude.
It is recognized that there have been no reported cases of meningoencephalitis reported among p'ver plant personnel to date; however, the seriousness of the disease (if contracted) and the confirmed presence of Naeglaria at four plants, leads us to inform all licensees with closed cycle cooling water systems of the potential occupational hazard and advise that they take appropriate action.
No written response to this IE Information Notice is required.
If you desire additional information regarding this matter, contact the Dire.ctor of the appropriate NRC Regional Office.
b
IE Information Notice No. 80-09 Enclosure March 7, 1980 RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Date Issued To Notice No.
Issued 80-09 Possible Occupational Health 3/7/80 All holders of Reactor Hazard Associated With Closed OLs and to near term Cooling Systems for Operating CP applicants Power Plants 80-08 The States Company Sliding 3/7/80 All power reactor Link Electrical Terminal facilities with an OL Block or a CP 80-07 Pump Shaft Fatigue Cracking 2/29/80 All Light Water Reactor Facilities holder power reactor Ols and cps 80-06 Notification of Significant 2/27/80 All holders of Reactor Events OLs and to near term OL applicants 80-05 Chloride Contamination 2/8/80 All licensees of nuclear of Safety Related Piping power reactor facilities and applicants and holders of nuclear power reactor cps 80-04 BWR Fuel Exposure in 2/4/80 All BWR's holding a Excess of Limits power reactor OL or CP 80-03 Main Turbine Electro-1/31/80 All holders of power Hydraulic Control System reactor OLs and cps 80-02 8X8R Water Rod Lower 1/25/80 All BWR Facilities End Plug Wear holder power reactor OLs or cps 80-01 Fuel Handling Events 1/4/80 All holders of power reactor OLs and cps 79-37 Cracking in Low Pressure 12/28/79 All power reactor OLs Turbine Discs and cps 79-36 Computer Code Defect in 12/31/79 All ppwer reactor OLs Stress Analysis of Piping and cps Elbow y