Forwards IE Info Notice 80-09, Possible Occupational Health Hazard Associated W/Closed Cooling Sys for Operating Power Plants. No Written Response Required
ML19290F059
Person / Time
Site: Rancho Seco
Issue date: 03/07/1980
From: Engelken R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
To: Mattimoe J
SACRAMENTO MUNICIPAL UTILITY DISTRICT
References
NUDOCS 8003180021
Download: ML19290F059 (1)


Text

f g

n pn ucco,'o a

-/_

UNITED STATES y W "-,.q g

NUCLEAR REGULATORY COMMISSION

.s REGION V o, A

[

1990 N. CALtFORNIA BOULEVARD

[

SUITE 202, WALNUT CREEK PLAZA WALNUT CREE K, CALIFORNI A 94596 March 7, 1980 Docket No. 50-312 Sacramento Municipal Utility District P. O. Box 15830 Sacramento, California 95813 Attention: Mr. John J. Mattimoe Assistant General Manager Gentlemen:

The enclosed IE Information Notice is forwarded to you for information.

No written response to this Information Notice is required.

If you have any questions related to the subject, please contact this office.

Sincerely,

[

w,55.-

R. H. Engelken Director

Enclosures:

1.

IE Information Notice No. 80-09 2.

List of Recently Issued IE Information Motices cc w/ enclosure:

R. J. Rodriguez, SMUD L. G. Schwieger, SMUD 8 0 0 3 1 E OO3d

SSINS:

6870 Accession No.:

UNITED STATES 7912190681 NUCLEAR REGULATORY COMftISSION 0FFICE OF INSPECTION AND ENFORCEMErlT 3

WASHINGTON, D.C.

20555 vo D

56

~

March 7, 1980 IE Information Notice No. 80-09 POSSIBLE OCCUPATIONAL HEALTH HAZARD ASSOCIATED WITH CLOSED COOLING SYSTEMS FOR OPERATING POWER PLANTS As a result of information that the causative agent for meningoencephalitis, the amoeba flaeglaria fowleri, had been found in warm water ponds in Florida and Texas where two fatalities were reported, NRC initiated a study by Oak Ridge National Laboratory on the occurrence of Naealaria in power plants with closed cycle cooling systens.

For seven power stations examined (6 fossil, 1 nuclear), this study confirmed the presence of pathogenic Naeglaria at three plants including the nuclear plant (Dresden).

Recently, Northern States Power Company (NSP), while monitoring the Prairie Island Nuclear Generating Plant closed cooling system for the amoeba, did identify the presence of Naeglaria. Although the Minnesota Department of Health does not consider the existence of the organism to be a public health threat, it was recognized as a possible occupational health hazard.

Plant personnel were instructed to wear rubber gloves when coming into contact with the circulating water and to wear respirators when working in the area of the cooling towers.

In November 1979, NSP conducted a special chlorination program at Prairie Island that was designed by Dr. Richard Tyndall of Oak Ridge to eradicate this organism.

Chlorine concentrations in the circulating water system was raised to 2.0 mg/l (measured as free chlorine) for a period of six hours to destroy both the amoebae and its encysted form.

This program also included dechlorination prior to discharge and intensive monitoring to document chlorine concentrations, the impacts of chlorinated cooling tower draft and sampling to determine the efficacy of the special chlorination program in destroying Maeglaria.

Preliminary results indicate that the program was successful in reducing the number of organisms present by two to three orders of magnitude.

It is recognized that there have been no reported cases of meningoencephalitis reported among power plant personnel to date; however, the seriousness of the di' :ase (if contracted) and the confirmed presence of Naealaria at four plants, h is us to inform all licensees with closed 9cle cooling water systems of the potential occupational hazard and adviN that they take appropriate action.

No written response to this IE Information Notice is required.

If you desire additional information regarding this matter, contact the Director of the appropriate NRC Regional Office.

~

IE Information Notice No. 80-09 Enclosure March 7,1980 RECENTLY ISSUED IE INFORMATION NOTICES Information Subject Date Issued To Notice No.

Issued 80-08 The States Company Sliding 3/7/80 All power reactor Link Electrical Terminal facilities with an OL Block or a CP 80-07 Pump Shaft Fetigue Cracking 2/29/80 All Light Water Reactor Facilities holder power reactor OLs and cps 80-06 Notification of Significant 2/27/60 All holders of Reactor Events OLs and to near term OL applicants 80-05 Chloride Contamination 2/8/80 All licensees of nuclear of Safety Related Piping power reactor facilities and applicants and holders of nuclear power reactor cps 80-04 BUR Fuel Exposure in 2/4/80 All BWR's holding a Excess of Limits power reactor OL or CP 80-03 Main Turbine. Electro-1/31/80 All holders of power Hydraulic Control System reactor OLs and cps 80-02 8X8R Water Rod Lower 1/25/80 All BWR Facilities End Plug Wear holder power reactor OLs or cps 80-01 Fuel Handling Events 1/4/80 All holders of power reactor OLs and cps 79-37 Cracking in Low Pressure 12/28/79 All power reactor OLs Turbine Discs and cps 79-36 Computer Code Defect in 12/31/79 All power reactor OLs Stress Analysis of Piping and cps Elbow 79-35 Control of Maintenance 12/31/79 All power reactor facilities and Essential Equipment with an OL or CP 79-34 Inadequate Design of 12/27/79 All holders of power reactor Safety-Related Heat OLs and cps Exchangers