DUKE POWER COMPANY Powra DUILDING 4a2 SocTu Cut:ncu STnzer, CHARI.oTTE, N. C. 26242 wwiu o..an n ea sa.

tiarch 12, 1980 WCr Pets,OENT

' tic e=c%g.* Anta 7 0 4 Seta= Paoovctio*

273-4083 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C.

20555 Attention:

Mr. Robert L. Baer, Chief Light Water Reactor Branch No. 2

Reference:

McGuire Nuclear Station Units 1 and 2 Docket Nos. 50-369, -370

Dear Mr. Denton:

As requested by your letter of February 12, 1980 which discussed deficiencies in the rod drop analysis for McGuire Nuclear Station, the following coc:mit-ment is made to enhance protection against dropped control rod events. These commitments may be modified pending Westinghouse's review of this subject.

In the manual mode of reactor control from 0 to 100% reactor power there will be no change in current McGuire operating procedures.

In automatic mode of reactor control from 0 to 90% reactor power there will be no change from current McGuire operating procedures.

In the automatic mode of reactor con-trol from greater than 90% reactor power control rod Bank D must be withdrawn greater than or equal to 215 steps. These restrictions will be incorporated into station operating procedures and Technical Specifications as appropriate.

Very truly yours,

/Q&'Q 0

< !^ *

/' W William O. Parker, Jr.

LJB:ses

\\

D 1

s o ns 1 rog