ML19290E556

From kanterella
Jump to navigation Jump to search
Satisfies Commitment in Util to Provide Results of SEP Seismic Review.All Accessible Floor Mounted safety-related Electrical Equipment Is Positively Anchored. Inaccessible Items Will Be Inspected at Later Date
ML19290E556
Person / Time
Site: Dresden 
Issue date: 03/10/1980
From: Janecek R
COMMONWEALTH EDISON CO.
To: Ziemann D
Office of Nuclear Reactor Regulation
References
NUDOCS 8003140203
Download: ML19290E556 (1)


Text

Commonwealth Edison One First National Plaza. Chicago. liknois Address Reply to Post Ofhee Box 767 Chicago. litinois 60690 March 10, 1980 Mr. Dennis L.

Ziemann, Chief Operating Reactors - Branch 2 Division of Operating Reactors U.S. Nuclear Regulatory Commission Washington, DC 20555

Subject:

Dresden Station Unit 1 SEP Seismic Review NRC Docket No. 50-10 Reference (a):

R. F.

Janecek letter to D.

L.

Ziemann dated February 29, 1980

Dear Mr. Ziemann:

This letter satisfies the commitment in Reference (a) to provide the results of our review of the anchorage existing for floor mounted safety related electrical equipment at Dresden Unit 1.

A list consisting of 76 items of floor mounted safety related electrical equipment was developed for the inspection.

All the equipment which was accessible for inspection has been determined to have postive a'chorage.

Those items which could not be taken out of service for inspection were the 4KV switch gear buses 11 and 12, MCC 4 and AC, and several distribution panels.

Based on the results of the inspection of accessible equipment, we have no reason to doubt that positive anchorage of this equipment also exists.

The. items not inspected at this time will be taken out of service and inspected as part of the overall seismic reevaluation of the plant, prior to startup from the current outage.

Please address any questions you may have concerning this matter to this office.

One (1) signed orignal and thirty-nine (39) copies of this transmittal are provided for your use.

Very truly yours,

/W Robert F.

Janecek Nuclear Licensing Administrator Boiling Water Reactors 80031 n) 2. Q

_,,