APPENDIX A NOTICE OF VIOLATION Duquesne Light Company Docket No. 50-412 This refers to the inspection conducted by representatives of the Region I (Philadelphia) office at the Beaver Valley Power Station, Unit 2, Shippingport, Pennsylvania of activities authorized by NRC License No. CPPR-105.
During this inspection, conducted on November 6-8, 1979, the following apparent item of noncompliance was identified:
10 CFR 50, Appendix B, Criterion XIII, states, in part, that:
" Measures shall be established to control the... storage... and preservation of material... in accordance with work and inspection instructions to prevent damage or deterior-ation."
Section 17.2.1.13A of Chapter 17 of the PSAR states, in part, that:
"The Duquesne Light Company Quality Assurance Program establishes measures to con-trol... storage... and preservation of material... in accordance with work and inspection instructions to prevent damage or deterioration."
Duquesne Light Company Receiving Inspection Plans RIP-59-2-R2 and RIP-59-R2 require that variable spring hangers be stored in accordance with Level C requirements.
Stone and Webster Design Specification 2 BVS-59, " Design and Fabrication of Power Plant Piping Supports," Revision 0, requires that threads and machined surfaces of piping supports shall be coated with a preservative. to 2 BVS-981 requires that fabricated piping supports be recoated, repainted or resealed as necessary during storage.
Contrary to the above, as of November 8, 1979:
Variable spring hangers were stored in Level D type storage; There was no requirement in applicable procedures to verify pre-servation of threads prior to storage nor was there an effective program to maintain preservation during storage.
As a result, rusting of threaded portions of stored hanger assemblies had oc-curred.
This item is an infraction.