bec to DAC:ADM:

o UNITED STATES CENTRAL FILES

[ e asc,"'o NUCLEAR REGULATORY COMMISSION PDR:HQ 3'

" ' ^

R EGION IV LPDR n

5,!

,o 611 RY AN PLAZ A oRIVE, SUITE 1000

-TIr E

':[

ARLINGTON, TEX AS 76012

/

%')

-s November 26, 1979 Docket No. 50-267 Public Service Company of Colorado ATTN:

Mr. C. K. Millen Senior Vice President P. O. Box 840 Denver, Colorado 80201 Gentle =en:

The enclosed IE Circular 79-23 is forwarded to you for your infor=ation.

No written response to this circular is required.

If you have any questions related to the subject, please contact this office.

Sincerely,

,g

~

K. V. Seyfrit Director

Enclosures:

1.

IE Circular No. 79-23 2.

List of Plants That May Have Received Defective Starter or Contactors 3.

List of Recently Issued IE Circulars cc:

D. W. Ware = bourg, Nuclear Production Manager Fort St. Vrain Nuclear Station I729 lQ P. O. Box 368 Platteville, Colorado 80651 L. Brey, Manager, Quality Assurance 80u100002-3 Q

UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 IE Circular No. 79-23 Date:

November 26, 1979 Page 1 of 1 MOTOR STARTERS AND CONTACTORS FAILED TO OPERATE Gould, Inc., Electrical Products Group, reported to the NRC on September 11, 1979 potential defects in certain NEMA Size 3, Starters and Contactors.

A possible binding or seisure of the carrier assembly, within the support plate of the stationary contact assembly, is caused by an undersized dimension of the support legs.

Starters and contactors with date code 7822 to 7935, model and serial numbers A10, All, A12, A13, A14, A20, A21, A22, and P10 are involved.

Faulty units were manufactured and distributed between June 1, 1978 and August 30, 1979.

The attached listing of nuclear plants, which have received some of this motor control equipment, represents a preliminary check of shipment records.

This listing, however, may not be complete.

Gould, Inc., will recall uninstalled items for retrofit and has retrofit kits available for field installation.

Based on the above, licensees are advised to verify all motor starter and contactor shipments received from Gould, Inc., between June 1, 1978 and August 30, 1979, and assure that applicable model and serial number components are corrected by retrofit and subsequent electrical operation tests.

No written response to this Circular is required.

If you desire additional information regarding this matter, contact the Director of the appropriate NRC Regional Office.

1729 105 DUPLICATE DOCUMENT Entire document previously l

entered to system u i

ANO No. of pages: