bcc to DAC:ADM:

@[p QCoq'o UNITED STATES CENTRAL FILES

?

NUCLEAR REGULATORY COMMISSION g

PDR:HQ REGloN IV O i 3 o

611 RY AN PLAZA DRIVE, SUITE 100o LPDR

% (r;

. j ARLINGTON, TEX AS 76012

- TIC ~

\\

/

NSIC November 26, 1979 Docket No.

50-285 Omaha Public Power District ATTN:

W. C. Jones, Division Manager -

Production Operations 1623 Harney Street Omaha, Nebraska 68102 Gentlemen:

The enclosed IE Circular 79-23 is forwarded to you for your information.

No written response to this circular is required.

If you have any questions related to the subject, please contact this office.

Sincerely, 9

l K. V. Seyfri Director

Enclosures:

1.

IE Circular No. 79-23 2.

List of Plants That May Have Received Defective Starter or Contactors 3.

List of Recently Issued IE Circulars cc:

S. C. Stevens, Manager Fort Calhoun Station Post Office Box 98 1729 102 Fort Calhoun, Nebraska 68102 8 0 010 90 c LZ-Q

e UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 IE Circular No. 79-23 Date:

November 26, 1979 Page 1 of 1 79 to 2 5' O 446 MOTOR STARTERS AND CONTACTORS FAILED TO OPERATE Gould, Inc., Electrical Products Group, reported to the NRC on September 11, 1979 potential defects in certain NEIIA Size 3, Starters and Contactors.

A possible binding or seisure of the carrier assembly, within the support plate of the stationary contact assembly, is caused by an undersized dimension of the support legs.

Starters and contactors with date code 7822 to 7935, model and serial numbers A10, All, A12, A13, A14, A20, A21, A22, and P10 are involved.

Faulty units were manufactured and distributed between June 1, 1978 and August 30, 1979.

The attached listing of nuclear plants, which have received some of this motor control equipment, represents a preliminary check of shipment records.

This listing, however, may not be complete.

Gould, Inc., will recall uninstalled items for retrofit and has retrofit kits available for field installation.

Based on the above, licensees are advised to verify all motor starter and contactor shipments received from Gould, Inc., between June 1, 1978 and August 30, 1979, and assure that applicable model and serial number components are corrected by retrofit and subsequent electrical operation tests.

No written response to this Circular is required.

If you desire additional information regarding this matter, contact the Director of the appropriate NRC Regional Office.

1729 103 DUPLICATE DOCUMENT Entire document previously AN No. of pages: