Forwards LERs 79-064/03L-0 & 79-067/03L-0
Date released: 10/30/2019 Download: ML19289F334


LER 79-067/03L-0 on 790504:radiation Monitoring Channel RM-RMS-159 Was Declared Inoperable Due to Filter Drive Failure.Caused by Failure of Slow Speed Motor Shaft on Paper Drive.Filter Paper & Motor Shaft to Be Replaced
ML19289F337
Person / Time
Site: North Anna Dominion icon.png
Issue date: 06/01/1979
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19289F337 (2)
LER 79-064/03L-0 on 790503:cooling Water Line to Superchargers on 1H Diesel Developed Leak at Threaded Connection.Possibly Caused by Incomplete Cleaning of Threads & Insufficient Torquing of Connection During Installation
ML19289F336
Person / Time
Site: North Anna Dominion icon.png
Issue date: 06/01/1979
From: Cartwright W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19289F336 (1)