ML19289C931

From kanterella
Jump to navigation Jump to search
Interim Rept Re Defective End Casting on 2-RS-PM-1B Recirculation Spray Pump Motor,Causing Bearing Grease Leakage & Consequent Gross Failure of Lower Bearing & Damage to Motor Shaft,Upper Guide Bearing & Upper & Lower Seals
ML19289C931
Person / Time
Site: North Anna 
Issue date: 01/22/1979
From: Brown S
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-PT21-79-096-000 043, 43, NUDOCS 7901290001
Download: ML19289C931 (3)


Text

.

T

\\

ATTACHED IS PART 21 REPORT FR011 IE MAIL UNIT - ROO!! 317 E/W

//

j i

PART 21 IDENTIFICATION N0.

COMPANY NAME

()%

79 - o 9c; - o o o DOCKET N0.

So-339 I

DATE OF LETTER i/.2.:L/7cf DATE Dif RIBUTED

'//a3 / fp

-l ORIGINAL REPORT l

SUPPLEf1ENTARY l

DISTRIBUTION:

l REACTOR (R)

FUEL CYCLE AND SAFEGUARDS (S)

MATERI ALS(ii)

I NRR/ DOR (Stello)

NMSS/FC&MS NRR/ DOR (Stello)

I NRR/DFri(Boyd)

AD/FF&MSI NMSS/SG f

l AD/ROI (Sniezek/Seyfrit)

PDR AD/SG-IE AD/RCI MPA/ PERFORMANCE EVALUATION BP,.

AD/R0I F2;B 12105 MPA/ PERFORMANCE EVALUATION LR. REGIONS REGIONS 12iB 12105 REGIONS NSIC MPA/ PERFORMANCE FvAL-j UATION BR. MNB1210_}

PDR TIC PDR l

LPDR IE FILES (2)

LPDR i

M CENTRAL FILES-SS 396 NSIC f

CENTRAL FILES (CHR0i!)

TIC i

liiE R A- >

.~

m l

IE FILES (2)

IE FILES (2) l l

CENTRAL FILES 016 CENTRAL FILES 016 CENTRAL FILES (CHRON)

CENTRAL FILES (CHROM) =

j CENTRAL FILES - SS 396-i' ACTION:

i PRELItilNARY EVALUATION OF THE ATTACHED REPORT INDICATB LEAD RESPONSIBILITY FOR FOLLON-UP AS SH0'.lN BELON:

O NRR C NMSS O OTHER [

ROI FFMS j

790129 coo 1 Y

1

7[ O f( - c)x

)

VG900

_,._,,,c.._.c_....-m, January 22, 1979 Mr. James P. O'Reilly, Director Serial fio. 043 Office of Inspection & Enforcement PSE&C/RBC:bep/mc U. S. fiuclear Regulatory Commission Region II Docket No. 50-339 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303

Dear Sir:

On January 17, 1979, a report was made under the provisions of 10CFR50.55(e) concerning a defective end casting on one of the Recirculation Spray Pump fttors. The defect permitted bearing grease leakage causing gross failure of the motor lower bearing.

In accordance with the reporting requirements of 10CFR21, the following information is submitted:

A.

Name and address of reporting individual:

Mr. E. A. Baum, Executive Manager Licensing and Quality Assurance Virginia Electric and Power Company P. O. Box 26666 Richmond, Virginia 23261 B.

Facility, activity, and/or component affected:

North Anna Power Station, Unit 2 Recirculation Spray Pump Motor 2-RS-PM-1B C.

Name of fina constructing the facility or supplying the component, activity or service.

General Electric Company AC Motor & Generator Division Vertical Motor Products Section 2155 South First Street San Jose, California 95112 D.

Description of defect, deficiency, or failure to comply:

A defect in the lower end casting of Recirculatirsn Spray Pump Motor 2-RS-PM-1B allowed grease to escape from the lower bearing during a test run of the motor.

The loss ~ of bearing lubricant caused gross failure of the lower bearing with resultant damage to the motor shaft, the upper guide bearing, and the upper and lower seal rings.

The problem was evidenced by noise and smoke emanating from the motor in the ninth hour of operation.

Motor

s VIRGNA RECTRIC AND POWER COMPANY TO Mr. James P. O'Reilly SH EET NO.

2 operation was terminated, and an examination revealed that bearing grease had leaked from a shrinkage cavity in the area of the grease relief plug in the lower end casting.

E.

Date of determination of reportability:

January 17, 1979 F.

Similar components, activities, or services:

One identical motor is used on Unit 2 at North Anna.

Identical motors are also used on North Anna Unit 1, Surry Unit 1, and Surry Unit 2.

G.

Corrective action which has been,.is being or will be taken, the indi-vidual responsible and the length of time to complete the action:

The motor will be returned to General Electric in San Jose, California for complete damage evaluation and repair.

All damaged parts will be replaced or repaired as deemed neces-sary by General Electric.

The lower end casting of the iden-tical motor installed in North Anna Unit 2 was field inspected, and no evidence of defectiveness was found.

Since the identi-cal motors in North Anna Unit 1 and Surry Units 1 and 2 have all operated in excess of thirty hours without incident, it is considered unlikely that a similar defect exists in their cast-ings.

The casting flaw appears to be an isolated case of gross shrinkage porosity rather than a generic imperfection.

Never-theless, visual inspections will be made on the identical motors used in North Anna Unit 1 and Surry 1 and 2 at the next outage.

H.

Other information:

Since no other actions will be required to correct the problem described in section D of this report, we consider this to be the final report under the provisions of 10CFR50.55(e)(3).

Should you require further information, please contact this office.

ers/truly ou 1

ll,

. h(!f a

Sa

. Brown, Jr.

Sen.ior Vice Presiden /

- Power Station Engineering hnd Construction cc:

Director, Office of Inspection andEnforcement(3)

.