~I dro,

UNITED STATES o

[e

'4 NUCLEAR REGULATORY COMMisslON E'; 1 7/

REGION 1 j

sa: PARK AVENUE

- % "?E xiNo oP Paussia. PENNsV L,V ANI A 19406 S.....

February 9,1979 Docket No. 50-333 Power Authority of the State of New York James A. FitzPatrick Nuclear Power Plant ATTN: Mr. J. D. Leonard Resident Manager P. O. Box 41 Lycoming, New York 13093 Gentlemen:

This Information Notice is provided as an early notification of a possibly significant matter.

It is expected that recipients will review the information for possible applicability to their facilities.

No specific action or response is requested at this time.

If further NRC evaluations so indicate, an IE Circular or Bulletin will be issued to recommend or request specific licensee actions.

If you have questions regarding the matter, please contact this office.

Sincerely, f

['fi Boyce H. Grier Director

Enclosures:

1.

IE Information Notice No. 79-03 2.

List of IE Information Notices Issued in 1979 79030G o 959=,

5 Power Authority of the State of New York 2

cc w/encls:

George T. Berry, General Manager and Chief Engineer P. W. Lyon, Manager - Nuclear Operations A. Klausmann, Director, Quality Assurance M. C. Cosgrove, Quality Assurance Supervisor J. F. Davis, Chairman, Safety Review Conmittee L. R. Bennett, Assistant General Manager - General Counsel G. M. Wilverding, Licensing Supervisor

.b UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C.

20555 IE Information Notice No. 79-03 Date:

February 9, 1979 Page 1 of 1 LIMITORQUE VALVE GEARED LIMIT SWITCH LUBRICANT Description of Circumstances:

At Commonwealth Edison reactors excessive failure rates of the Limitorque valve geared limit switches were being experienced.

Investigation revealed that the failure mode was a drying out and hardening of the Beacon 325 lubricant. Once hardening takes place, the brass gears within the limit switch become immobile and destroy themselves when an attempt is made to operate the valve.

The Limitorque Corporation has recommended Mobilgrease 28 as a replacement grease for switch applications where the temperature exceeds 140 degrees Fahrenheit. Tests conducted by Mobil and Limitorque Corporation indicate that Mobi1 grease 28, in addition to having a superior temperature rating, will satisfy the same environmental conditions and meet the same qualification parameters as Beacon 325.

All licensee and construction permit holders should consider conducting a review to vetermine if Beacon 325 lubricant is being used in geared limit switche.1 in environments conducive to drying out and subsequent hardening of the lubricant.

If conditions a re found to be conducive to failures, consideration should be giver to replacing the grease with a more suitable grease.

This information is provided as an early notification of a possibly significant. matter.

It is expected that recipients will review the information for possible applicability to their facilities.

No specific action or response is requested at this time.

If further NRC evalua-tions so indicate, an IE Circular or Bulletin will be issued to recom-mend or request specific licensee actions.

If you have questions re-garding this matter, please contact the Director of the appropriate NRC Regional Office.

Enclosure:

List of IE Information Notices Issued in 1979

s IE Information Notice No. 79-03 Date:

February 9,1979 Page 1 of 1 LISTING OF IE INFORMATION NOTICES ISSUED IN 1979 Information Subject Date Issued To Notice No.

Issued 79-01 Bergen-Paterson Hydraulic 2/2/79 All power reactor Shock and Sway Arrestor facilities with an Operating License (0L) or a Construction Permit (CP) 79-02 Attempted Extortion -

2/2/79 All Fuel Facilities Low Enriched Uranium