M190171 Docket 52-010 10 CFR 50.46 10 CFR 50.46(a)(3)(iii) 10 CFR Part 52, Appendix E October 9, 2019 US Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001
Subject:
ESBWR Design Certification Annual 10 CFR 50.46 Report for 2019
Reference:
- 1. Letter, M. P. Catts (GEH) to Document Control Desk (NRC), M190165, ESBWR Design Certification Annual 10 CFR 50.46 Report for 2019, October 8, 2019.
GE Hitachi Nuclear Energy (GEH), as the applicant for the ESBWR Design Certification (10 CFR Part 52, Appendix E), submits this annual report under 10 CFR 50.46, "Acceptance Criteria for Emergency Core Cooling Systems for Light-Water Reactors." Specifically, is the 2019 annual report for the ESBWR Design Certification for emergency core cooling system (ECCS) evaluation model changes or errors that affect the peak cladding temperature (PCT) calculation. This is an update to the previous report (Reference 1), due to the omission of two error notifications that were submitted during the last reporting period. The notifications were zero-degree effects on the PCT calculation, so, although these evaluation model errors are corrected, there will be no change to any reported analysis results.
By this letter, GEH also notifies the licensees, DTE Electric Company for Enrico Fermi Nuclear Plant Unit 3, and Dominion Virginia Power for North Anna Unit 3, in accordance with 10 CFR 50.46(a)(3)(iii), because the licenses for these units reference the ESBWR Design Certification.
Please contact me if you have any questions regarding this information.
GE Hitachi Nuclear Energy Michelle P. Catts Senior Vice President Regulatory Affairs 3901 Castle Hayne Road P.O. Box 780 M/C A-18 Wilmington, NC 28402 USA T 910 200-9836 Michelle.Catts@ge.com
M190171 Page 2 of 2 October 9, 2019
Sincerely,
Michelle P. Catts Senior Vice President, Regulatory Affairs Commitments: No additional commitments are made.
Enclosure:
- 1. ESBWR Design Certification 10 CFR 50.46 Annual Report - 2019 cc:
J. Colaccino, NRC M. Brandon, DTE R. Westmoreland, DTE D. Aitken, Dominion C. Sly, Dominion DBR-0033424 R4
M190171 ESBWR Design Certification 10 CFR 50.46 Annual Report - 2019
M190171 Page 1 of 1
ESBWR Design Certification 2019 Annual Report Under 10 CFR 50.46(a)(3)(iii)
Emergency Core Cooling System Model Plant Name:
ESBWR Design Certification (Docket 52-010; 10 CFR Part 52, Appendix E)
Utility Name:
GE Hitachi (as applicant for the ESBWR Design Certification)
Reporting Year: 2019*
Evaluation Model: TRACG LBPCT Net PCT Effect Absolute PCT Effect Analysis of Record Licensing Basis PCT (LBPCT), with prior updates 600°F A.
Prior 10 CFR 50.46 Changes or Error Corrections
- Previous years PCT =
+/- 0°F
+ 0°F B.
Prior 10 CFR 50.46 Changes or Error Corrections
- This year (itemized below):
PCT =
+/- 0°F
+ 0°F 2019 TRACG Channel Inlet Subcooling Calculation 0
2019 TRACG Radiation Heat Transfer Calculation 0
C.
Absolute Sum of 10 CFR 50.46 Changes PCT =
+ 0°F
+ 0°F Projected LBPCT based on these changes 600°F
- The reporting period is 10/29/2018 through 09/30/2019. The sum of the peak cladding temperature (PCT) from the most recent analysis using an acceptable evaluation model and the estimates of PCT effect for changes and errors identified because this analysis is less than 2,200°F.
Most Recent Previous Report (2019): Letter, M. P. Catts (GEH) to Document Control Desk (NRC),