ML19282B477
| ML19282B477 | |
| Person / Time | |
|---|---|
| Site: | Davis Besse |
| Issue date: | 03/08/1979 |
| From: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| To: | Jeffery Grant TOLEDO EDISON CO. |
| References | |
| NUDOCS 7903150046 | |
| Download: ML19282B477 (1) | |
Text
. - _ _ _.. _
7
. s -
dSeare%
UNITED STATES c
y e.
pt NUCLEAR REGULATORY COMMISSION j
,ljj REGloN lli
\\
g 7so nooseveLT noAo 6 g, e
OLEN ELLYN, ILLINots 60137
....+
NR -8.1979 Docket No. 50-346 Toledo Edison Company ATTN:
Mr. James S. Grant Vice President - Energy Supply Edison Plaza 300 Madison Avenue Toledo, OH 43652 Gentlemen:
The enclosed IE Bulletin No. 79-02 is forwarded to you for action. A written response is required.
If you desire additional information regarding this matter, please contact this office.
Sincerely,
&k A
James G. Kepple.r Director
Enclosures:
1.
List of IE Bulletins Issued in Last Twelve Months cc w/encls:
Mr. T. Murray, Station Superintendent Central Files Director,NRR/DPM Director, NRR/ DOR PDR Local PDR NSIC TIC U. Young Park, Power Siting Commission 7903150046
U.S. NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT REGION III March 8, 1979 IE Bulletin No. 79-02 PIPE SUPPORT BASE PLATE DESIGNS USING CONCRETE EXPANSION ANCHOR BOLTS Description of Circumstances:
While performing inservice inspections during a March-April 1978 refueling outage at Millstone Unit 1, structural failures of piping support for safety equipment were observed by the licensee.
Subsequent licensee inspections of undamaged supports showed a large percentage of the concrete anchor bolts were not tightened properly.
Deficiency reports, in accordance with 10 CFR 50.55(e), filed by Long Island Lighting Company on Shoreham Unit 1, indicate that design of base plates using rigid plate assumptions has resulted in underestima-tion of loads on some anchor bolts. Initial investigation indicated that near.ly fifty percent of the base plates could not be assumed to behave as rigid plates. In addition, licensee inspection of anchor bolt installations at Shoreham has shown over fifty percent of the bolt installations to be deficient.
Vendor Inspection Audits by NRC at Architect Engineering firms have shown a wide range of design practices and installation procedures which have been employed for the use of concrete expansion anchors.
The current trends in the industry are toward more rigorous controls and verification of the installation of the bolts.
The data available on dynamic testing of the concrete expansion anchors show fatigue failures can occur at loads substsntially below the bolt static capacities due to material imperfections or notch type stress risers. The data also show low cycle dynamic failures at loads below the bolt static capacities due to joint slippage.
Action to be Taken by Licensees and Permit Holders:
For pipe support base plates that use concrete expansion anchor bolts in Seismic Category I systems as defined by Regulatory Guide 1.29, " Seismic Design Classification" Revis, ion 1, dated August 1973 or as defined in the applicable FSAR.
1.
Ver{fy,that.,pirsgupwrJogM~e mW"F""3 accounted for in '