ML19282B473
| ML19282B473 | |
| Person / Time | |
|---|---|
| Site: | Bailly |
| Issue date: | 03/08/1979 |
| From: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| To: | Shorb E NORTHERN INDIANA PUBLIC SERVICE CO. |
| References | |
| NUDOCS 7903150040 | |
| Download: ML19282B473 (1) | |
Text
_
[R AEG%
UNITED STATES e
4 NUCLEAR REGULATORY COMMISSION
(
T*II E REGION 111 799 ROOSEVELT RoAo y,
g, GLEN E LLYN.1LLINolS 60137 NAR. -8.1979 Docket No. 50-367 Northern Indiana Public Service Company ATTN:
Mr. Eugene M. Shorb Senior Vice President 5265 Hohman Avenue Hammond, IN 46325 Gentlemen:
The enclosed IE Bulletin No. 79-02 is forwarded to you for action. A written response is required.
If you desire additional information regarding this matter, please contact this office.
Sincerely, 4.
ames G. Keppler
' Director
Enclosures:
1.
IE Bulletin No. 79-02 2.
List of IE Bulletins Issued in Last Twelve Months cc w/encls:
Central Files Director, NRR/DPM Director, hM/ DOR PDR Local PDR NSIC TIC Mr. Dean Hansell, Office of Assistant Attorney General 7903150040
U.S. NUCLEAR REGULATORY C0mi1SSION OFFICE OF INSPECTION AND ENFORCEMENT REGION III March 8, 1979 IE Bulletin No. 79-02 PIPE SUPPORT BASE PLATE DESIGNS USING CONCRETE EXPANSION ANCHOR BOLTS Description of Circumstances:
While performing inservice inspections during a March-April 1978 refueling outage at Millstone Unit 1, structural failures of piping support for safety equipment were observed by the licensee.
Subsequent licensee inspections of undamaged supports showed a large percentage of the concrete anchor bolts were not tigh;ened properly.
Deficiency reports, in accordance with 10 CFR 50.55(e), filed by Long Island Lighting Company on Shoreham Unit 1, indicate that design of base plates using rigid plate assumptions has resulted in underestima-tion of loads on some anchor bolts. Initial investigation indicated that near.ly fifty percent of the base plates could not be assumed to behave as rigid plates. In addition, licensee inspection of anchor bolt installations at Shoreham has shown over fifty percent of the bolt installations to be deficient.
Vendor Inspection Audits by NRC at Architect Engineering firms have shown a wide range of design practices and installation procedures which have been employed for the use of concrete expansion anchors.
The current trends in the industry are towcrd more rigorous controls and verification of the installation of the bolts.
The data available on dynamic testing of the concrete expansion anchors show fatigue failures can occur at loads substantially below the bolt static capacities due to material imperfections or notch type stress risers. The data also show low cycle dynamic failures at loads below the bolt static capacities due to joint slippage.
Action to be Taken by Licensees and Permit Holders:
For pipe support base plates that use concrete expansion anchor bolts in Seismic Category I systems as defined by Regulatory Guide 1.29, " Seismic Design Classification" Revision 1, dated August 1973 or as defined in the applicable FSAR.
1.
Verify that pipe support bana nlar. -f1-*
- m accounted for DUPLICATE DOCUMENT supporting anal I, base plates Entire document previously f