F'

,

>

j[

%,

UNITED STATES

'

h

'

NUC LE AR REGULATORY COMMISSION

..

j ,I

g

REGloN lif

i

g

  • A

,p

799 ROOSE VE LT RO AD

,

GLE N E LLY N, ILLINOb 60137

s," . j

.....

Docket No. 50-155

JAN 1 E 379

Consumers Power Company

ATTN:

Mr. R. B. DeWitt

Manager of Nuclear

Plant Operations

212 West Michigan Avenue

Jackson, MI

49201

Gentlemen:

This refers to the inspection conducted by Miss R. Greer of this

office on November 30 - December 1, 1978, of activities at Big

Rock Point Nuclear Plant authorized by NRC Operating License No.

DPR-6 and to the discussion of our findings with Mr. C. Hartman

and o:hers of your ctaff at the conclusion of the inspection.

The enclosed copy of our inspection report identifies areas

examined during the inspection. Within these areas, the

inspection consisted of a selective examination of procedures

and representative records, observations, and interviews with

personnel.

No items of noncompliance with NRC requirements were identified

during the course of this inspection. However, an area was

identified which needs management attention. We are concerned

about your use of the NaI detector to quantify effluent re-

leases. As discussed in paragraph 3 of the enclosed inspection

report, several disagreements resulted from your failure to

detect certain radionuclides using the NaI system. Although the

total activity that you quantified on the particulate filter was

approximately the same as the total activity reported by the NRC's

Reference Laboratory, the mr.ximum permissible concentrations con-

tained in 10 CFR 20 Appendix B are more restrictive for certain

radionuclides not detected by the NaI system than the concentra-

tions for the radionuclides reported (for example, Cs-134 and

Mn-54).

We are concerned that a future release could exceed

regulatory limits for a radionuclide not detected by the NaI system.

Please inform this of fice in writing within twenty days of your

receipt of this letter of the actions you will take to insure that

no regulat,ry limits are exceeded during the times you' consider it

absolutely necessary to quantify effluent releases using the NaI

detector.

'

7903 080 4fil

..

.

Consumers Power Company

-2-

JAN1L 379

In accordance with Section 2.790 of the NRC's " Rules of

Practice," Part 2, Title 10, Code of Federal Regulations, a

copy of this letter and the enclosed inspection report will

be placed in the NRC's Public Document Room, except as follows.

If this report contains information that you or your contractors

believe to be proprietary, you must apply in writing to this

office, within twenty days of your receipt of this letter, to

withhold such information from public disclosure.

The

applicntion must include a full statement of the reasons for

which the information is considered proprietary, and should be

prepared so that proprietary information identified in the

application is contained in an enclosure to the application.

We will gladly discuss any questions you have concerning this

inspection.

Sincerely,

h fn k%

TU

James G. Keppler

Director

Enclosure:

IE Inspection

Rp t No. 50-155/78-11

cc w/ encl:

Mr. C. J. Hartman, Plant

Superintendent

Central Files

Reproduction Unit NRC 20b

PDR

Local PDR

NSIC

TIC

Ronald Callen, Michigan Public

Service Commission

Anthony Roisman, Esq.,

Attorney