M 366 LICENSEE EVENT REPORT a

CONTf10L BLOCK: l l

l l

l l

lh (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATIONI 1

6 I s l c l s l E I p i l l@l 0 lo l 10 lo lo lo lo l lo lo l@h.11 li I, 11 l@l l@

9 LICENSEE CODE 14 16 LICENSE NuvBEM 25 26 LicENSt YvrE Jo 57 L A T $8 ERCE d l0l5l0l-10131215 @l1 12 11 lo 17 17 @l0l1l019l7b l@

60 61 DOCKET NUMBE R 68 69 EVENT DATE 74 7b REPORf DATE 80 EVENT DESCRIPTION AND PROB ABLE CONSEQUENCES h M eu hvin-lAfter performine an E.C.C.S. load secuencing ence-diennt gnnnenent received.

The 1

1remotelv secured from the control room when a reverse power alarm wac l diesel generator output breaker was tripped by the control operator and em ke vu 1

Iobserved to be coming from 32D relay. When the cover for the 32D. Directional Power I 1

IRelay, was removed, the relay started to flane and was cytingefehoA bv n roch-icene.

lWhen the diesel generator output breaker door was opened. the diesel lockour enlov l

l l86DB, was also found flaming and was extinguished.

9 COMP.

VALVE SYSTEM CAUSE CAUSE CODE CODE SUBOODE COMPONENT CODE SV8 CODE SUBCODE AIYIXl@ W h (J_jh IElE h (h l Zlh I RI EI L I

9 10 11 12 TJ 18 19 20 SE QUENTI AL OCCURRENCE REPORT Revision LER EVENT YE AR REPORT NO.

CODE TYPE NO.

@, agog /RO 17171 l-- _]

I1 1 il W

1014I W

[--J L.c_J

_ 21 22 23 24 26 27 28 29 3J 31 32 T K N C ON PL NT METH O HOURS 58 i FOR S

L R MAN FA TURER G ol8 ol@

[A,,,j@l2_.j@

(J_ j@

l 2lh 0l 0l 0l 0l d@

W@

W@

33 34 3b 36 37 40 41 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h 'ufring was checked and l

INo cause for the f ailure was dere-innd All enlmv enveral laced. recalibrated. and checked.

Tha PAnF l lfound to be correct. The 32D relay was r The 86DBl l relay coil was replaced, the contacts cleaned, and the relay action checked.

l relay was then installed and recalibrated. The relay circuits were then visually l checked and trip checked.

(See attached) l so 9

A

% POWE R OTHER STATUS DISCO RY DISCOVERY DESCRIPTION W@ l1 lo lo l@l NA l

W @l Surveillance Test l

A$nviTV cOOTEwT tocu,0NO,REuAsE@

AMOU~T O, ACTiviTv @ i I

mu AsEo o, Riu AsE i n iz_J @ [_z_J@l n 30 44 46 9

to 11 PERSONNEL E XPOSURE5 NUMSER rYPE DE SCRIPTION I

IoIoIol@[.z.j@l n

nRsON~d%ULs oEsCRI,TiO~@

i

,,UM.ER lololol@l n

9 11 12 LOS5 OF OR DauAGEO~TO FACILITY @

7904060 Wj Tvn oEsCRin I

Lzj@l n

9 to u m$

SCRIPTION sfut i

i i ir i i i i i

i i

LER CONTINUATION -- RO# 1-77-111 Facility:

_BSEP Unit #1 Event Date:

12-10-77 CAUSE DESCRIPTION CON'T.:

A followup check will be made with the relay manufacturer to ensure that this type of relay does not have a history of failures.

If any problems are uncovered, an additional report will be submitted.