First Interim Rept on Failure of Control Loop Bistables on 790214:bistables in Auxiliary Control Room Found to Fail in Undesirable Position Upon Loss of Control Power.Caused by Error in Instrument Wiring
ML19273B440
Person / Time
Site: Sequoyah  Tennessee Valley Authority icon.png
Issue date: 03/14/1979
From:
TENNESSEE VALLEY AUTHORITY
To:
Shared Package
ML19273B439 List:
References
NUDOCS 7904060359
Download: ML19273B440 (1)


Text

_ -__

ENCLOSURE SEnUOYAH NitCLEAR PLANT UNITS 1 AND 2 CONTFOL LOOP BISTABLES FAIL TO UNDESIRABLE POSITION ON LOSS OF COMTROL POMEP NCR MEB 79-10 FIRST INTERIM REPORT Descrintion of Deficiency Bistables associated with certain control loops in the Auxiliary Control Room have been found to fail in an undesirable position on loss of control power. This was due to an error in the viring of the instrumentation.

The problem does not exist in the Main Control Room instrumentation.

Interin Proeress The problem has been identified and the Electrical Engineering Branch and the Seouovah-Watts Bar Project are jointiv reviewinn the Auxiliary Control Room instrumentation for other instat.ces of this problem.

VSO406D559