'l

~

Telecopied to Mr. O'Reilly and Mr. Furr 12-12-79 C

5 :1(.,0, I i.

Carolina Power & Light Company m.-

' [. [ [ l 8 5b B

svick Steam Electric Plant P. O. Box 458 Southport, N. C.

28461 December 12, 1979 FILE: B3516 SERIAL: BSEP/79-1219 Mr. James P. O'Reilly, Director U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NO. 1 LICENSE NO. DPR-71 DOCKET NO. 50-325 CONFIRMATION: FACSIMILE FOR AN IMMEDIATELY REPORTABLE EVENT (1-79-107)

Dear Mr. O'Reilly:

This facsimile confirms the conversation between Mr. J. M. Brown, Operard.ons Manager, and Mr. P. Kellogg, of your office, at 1600 on December 12,19"<9.

While performing PT 19.6,0.1, Visual Inspection of Inaccessible Snubbers, snubbers B21-34SS296, B21-34SS297, B21-34SS299, B21-34SS336, B21-34SS339, and B21-34SS340, all downstream of main steam safety relief valve B21-F013H, were found inoperable. It is believed that this damage occurred following a reactor scram on November 20, 1979, when safety relief valves F013F, G, and H autenati-cally lifted. An inspection of all snubbers in the drywell is in pro; tress at this time.

This event is 'rsported un:er Technical Specifications 6.9.1.81.

Very truly yours, d

A. C. Tollison, Jr., General Manager Brunswick Steam Electric Plant RMP/cbf cc: *Mr. B. J. Furr

\\

8001080 6 5 2.

4 g