Notice of Deviation for Insp on 781205-08
ML19270F052
Person / Time
Site: South Texas  
Issue date: 12/20/1978
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML17195A451 List:
References
50-498-78-17, 50-499-78-17, NUDOCS 7901250085
Download: ML19270F052 (1)


Text

,50-498/78-17 C

50-499/78-17 Appendix A fl0TICE OF DEVIATION Based on the results of the flRC inspection conducted December 5-8, 1978, it appears that certain of your activities deviate from commitments made in your Preliminary Safety Analysis Report as indicated below:

Reporting of Cadwelder Qualification Inspection and Test Results by Level I Inspector Section 3.8.1.2.4, " Summary of Plant Principal Specifications," of the South Texas Project PSAR states that applicable sections of the ASME-ACI-359 document are included in plant principal specifications in regard to construction techniques, examination and testing.

Article VII-4100 of the ASME-ACI-359 document states that Level II is the minmum level of capability allowed for personnel who report inspection and test results.

Contrary to the above:

Brown & Root Quality Assurance Department Cadwelder Qualification Reports for Cadwelders 42, 43, 47, 48, 49, 50 and 51, which were prepared in August and October 1978, were signed in the " Reported by" block by Level I @ inspectors.

This is a deviation.

7901'25008 1