Forwards LER 79-054/01T-0
Date released: 10/10/2019 Download: ML19269E409


LER 79-054/01T-0 on 790615:cracks in 4,160 Volt Emergency Sys Nonsegregated Bus Insulation Sleeving Observed.Caused by Incompatibility Between Lexan Sleeving Matl & Versa-Fab Varnish Tape.Cracks Repaired W/Recommended Tape
ML19269E411
Person / Time
Site: Crystal River 
Issue date: 06/15/1979
From: Cooper J
FLORIDA POWER CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19269E411 (2)
Forwards LER 79-054/01T-0
ML19269E408
Person / Time
Site: Crystal River 
Issue date: 06/25/1979
From: Stewart W
FLORIDA POWER CORP.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19269E408 (1)