  1. "%,k d

4 UNITED STATES j

8-NUCLEAR REGULATORY COMMISSION f,)*I, h

{..

REGloN 111

  • i f

799 ROoSEVE LT ROAD g,;

,e otes ettvs.itti~o S eoia7 s,

FEBD J79 Docket No. 50-266 Docket No. 50-301 Wisconsin Electric Power Company ATTN:

Mr. Sol Burstein Executive Vice President Power Plants 231 West Michigan Milwaukee, WI 53201 Centlemen:

This Information Notice is provided as an early notification of a possibly significant matter. It is expected that recipients will review the information for possible applicability to their facili-ties. No specific action or response is requested at this time.

If further NRC evaluations so indicate, an IE Circular or Bulletin will be issued to recommend or request specific licensee actions.

If you have questions regarding the matter, please contact the Director of the appropriate NRC Regional Of fice.

Sincerely,

& $ h((k ---

VJames G. Ke ler Director

Enclosures:

1.

IE Information Notice No. 79-03 2.

List of IE Information Notices Issued in 1979 cc w/encls:

Mr. G. A. Reed, Plant Manager Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR NSIC TIC Sandra A. Bast, Lakeshore Citizens for Safe Energy 7902279gqq

J U.S. NUCLEAR RECULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT RECION III February 9, 1979 IE Information Notice No: 79-03 LIMITORQUE VALVE GEARED LIMIT SWITCH LUBRICANT Description of Circumstances:

At Co=monwealth Edison reactors excessive failure rates of the Limitorque valve geared limit switches were being experienced.

Investigation revealed that the failure mode was a drying out and hardening of the Beacon 325 lubricant. Once hardening takes place, the brass gears within the limit switch become immobile and destroy themselves when an attempt is made to operate the valve.

The Limitorque Corporation has recom= ended Mobilgrease 28 as a replacement grease for switch applications where the temperature exceeds 140 degrees Fahrenheit.

Tests conducted by Mobil and Limitorque Corporation indicate that Mobilgrease 28, in addition to having a superior temperature rating, will satisfy the same environmental conditions and meet the same qualification parameters as Beacon 325.

All licensee and construction permit holders should consider conducting a review to dete rmine if Beacon 325 lubricant is being used in geared limit switches in environments conducive to drying out and subsequent hardening of the lubricant.

If conditions are found.to be conducive to failurcs, consideration should be given to replacing the grease with a more suitable grease.

This information.is previded as an early notification of a possibly signlficant matter.

It is expected that recipients will review the information for possible. applicability to their-facilities.

No. specific action or response is requested at this time.

If further NRC evalua-tions so-indicate, an IE-Circular _or Bulletin will be issued to recom-mend or request specific licensee actions. If you have questions regarding this matter, please contact the Director of the appropriate NRC Regional Offi'

Enclosure:

List of IE Information Notices Issued in 1979 DUh 7902150358

IE Information Notice No. 79-03 February 3, 1979 LISTING OF IE INFORMATION NL'" ICES ISSUED IN 1979 Informat?sn Subject Date Issued To Notice No.

Issued 79-01 Bergen-Paterson Hydraulic 2/2/79 All power reactor Shock and Sway Arrestor facilities with an OL or a CP 79-02 Attempted Extortion -

2/2/79 All Fuel Facilities Low Enriched Uranium