ML19263E591

From kanterella
Jump to navigation Jump to search
Forwards IE Info Notice 79-13, Indication of Low Water Level in Oyster Creek Reactor
ML19263E591
Person / Time
Site: Callaway  
Issue date: 05/29/1979
From: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To: Bryan J
UNION ELECTRIC CO.
References
NUDOCS 7906200139
Download: ML19263E591 (1)


Text

ik hf'th en maco UNITED STATES f*

NUCLEAR REGULATORY COMMISSION,

[$

i ie g

nEctoN W 4

7.k"',~6[/j

' DJ no noosevett nono a

corn retvu. itusois soin

+.,*....f Docket No. 50-483 NAY 2 9 M Docket No. 50-486 Union Electric Company ATTN:

Mr. John K. Bryan Vice President - Nuclear P. O. Box 149 St. Louis, MO 63166 Gentlemen:

This Information Notice is provided as an early notification of a possibly significant matter.

It is expected that recipients will review the information for possible applicability to their facilities.

No specific action or response is requested at this time.

If further NRC evaluations so indicate, an IE Circular or Bulletin will be issued to recommend or request specific licensee actions.

If you have questions regarding this matter, please contact the Director of this office.

Sincerely, C

,h )d mf - -

fJames G. Kep" pier Director

Enclosure:

IE Information Notice No. 79-13 cc w/ encl:

Mr. W. H. Weber, Manager, Nuclear Construction Central Files Director, NRR/DPM Director, NRR/ DOR PDR Local PDR Nbb 0

NSIC TIC Region I & IV Ms. K. Drey Hon. C. J. Frass, Chairman Missouri Public Service Commission 7906200159

~

U.S. TUC1 EAR REGULATORY COMMISSION N

OFFICE OF INSPECTION AND ENFORCEMENT REGION III May 29, 1979 IE Information Notice No. 79-13 INDICATION OF LOW WATER LEVEL IN THE OYSTER CREEK REACTOR Su==arv A loss of feedwater transient at the Oyster Creek facility on May 2, 1979, resulted in a significant reduction in water inventory within the reactor core shroud area as measured by one set of water level instruments (triple low level), while the remaining level instruments, sensing from the reactor annulus area indicated water levels above any protective feature setpoint (Figure 1).

The water level within the core shroud area was reduced below the " triple lov level" setpoint of 4-feet, 8-inches above the top of the fuel.

Subsequent analysis by the licensee has determined that the minimum collapsed water level (solid, without steam voids) over the top of the fuel was 1 to 1-1/2 feet.

Coolant sample analyses and offgas release rates do not indicate any fuel damage occurred.

General Oyster Creek is a non-jet pu=p BWR with licensed power of 1930 MWt. The plant was first made critical May 3, 1969.

Status Before Transient Operating at near full power with the main parameters at levels as follows:

1895 MWt pov.. level 79" Yarway (13'4" over top of fuel) reactor water level 1020 psig reactor pressure 7.1x106 i/hr feedflov 14.8x104 gpm recirculation flow rate (4 pumps) 22Ob 12 psid core op Equipment Out of_Sgrvice (OOS "D" recirc pump 00S due to se DUPLICATE DOCUMENT "B" startup transformer 00S f Entire document previously entered into system under:

ANO A !!

N o.

of Pages:

.