  1. "8G0 UNITED STATES 9

g NUCLEAR REGULATORY COMMISSION f3

,}

REGloN lli g

799 ROOSEVELT RO AD e

h

\\'..... [

GLEN ELLYN ILLINots 60137 MAY 2 91979 Docket Nos. 50-10, 50-237, 50-249, 50-254, 50-265, 50-295, 50-304, 50-373, 50-374, 50-454, 50-455, 50-456 and 50-457 Commonwealth Edison Company ATTN:

Mr. Byron Lee, Jr.

Vice President Post Office Box 767 Chicago, IL 60690 Gentlemen:

This Information Notice is provided as an early notification of a possibly significant matter.

It is expected that recipients will review the information for possible applicability to their facilities.

No specific action or response is requested at this time.

If further hTC evaluations so indicate, an IE Circular or Bulletin will be issued to recommend or request specific licensee actions.

If you have questions regarding this matter, please contact the Director of this office.

Sincerely,

%S $

~

(/ James G. Kepp er Director

Enclosure:

IE Information Notice No. 79-13 cc w/ encl:

Mr. B. B. Stephenson, Mr. R. Cosaro, Project Station Superintendent Superintendent Mr. N. Kalivianakis, Central Files Station Superintendent Director, NRR/DPM Mr. N. Wandke, Station Director, NRR/ DOR Superintendent PDR Mr. L. J. Burke, Site Local PDR Project Superintendent NSIC Mr. T. E. Quaka, Quality TIC Assurance Supervisor Antbony Roisman, Esq.,

Mr. R. H. Holyoak, Station Attorney Superintendent Mr. Dean Hansell, Office Mr. Gunner Sorensen, Site of Assistant Attorney Project Superintendent General 2288 259 7906200070

U.S.' NUCLEAR REGULATORY COMMISSION Y

OFFICE OF INSPECTION AND ENFORCEMENT REGION III May 29, 1979 IE Information Notice No. 79-13 INDICATION OF LOW WATER LEVEL IN THE OYSTER CREEK REACTOR Su=.a ry A loss of feedwater transient at the Oyster Creek facility on May 2,1979, resulted in a significant reduction in water inventory within the reactor core shroud area as measured by one set of water level instruments (triple low level), while the remaining level instruments, sensing from the reactor annulus area indicated water levels above any protective feature setpoint (Figure 1).

The water level within the core shroud area was reduced below the " triple lov level" setpoint of 4-feet, 8-inches above the top of the fuel.

Subsequent analysis by the licensee has determined that the minimum collapsed water level (solid, without steam voids) over the top of the fuel was 1 to 1-1/2 feet.

Coolant sample analyses and offgas release rates do not indicate any fuel damage occurred.

General Oyster Creek is a non-jet pu=p BWR with licensed power of 1930 MWt. The plant was first made critical May 3, 1969.

Status Before Transient Operating at near full power with the main parameters at levels as follows:

1895 MWt power level 79" Yarway (13'4" over top of fuel) reactor water level 1020 psig reactor pressure 7.1x106 f /hr feedflow 14.8x104 gpm recirculation flow rate (4 pumps) 88 2 0 12 paid core op DUPLICATE DOCUMENT

',',D',,recire pump 00S due to e B startup transformer 00S F, tire document previously entered into system under:

nNo W65ft%5,//%.

No. of pages:

.