Responds to IE Bulletin 80-01.Plant Has hard-seat Check Valves.Valves Are Stainless Steel W/Stellite Seats.Entire Sys from Valve Operator Through Accumulator,Including Compressors,Is Redundant Seismic Class IE Sys
ML19262C233
Person / Time
Site: Brunswick  Duke Energy icon.png
Issue date: 01/17/1980
From: Furr B
CAROLINA POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
IEB-80-01, IEB-80-1, NUDOCS 8002080421
Download: ML19262C233 (1)


Text

~

N6

.l Cf S P f.

GS#

-u gn

. jf, C,,R E}' _. _.,

Carolina Power & Light Company 4, -..

January 17, 1980 3 J AN 22 r,9 : 4 0 FILE: NG-3513(B)

SERIAL: NO-80-077 Mr. James P. O'Reilly, Director U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, Suite 3100 Atlanta, GA 30303 BRUNSWICK STEAM ELECTRIC PLANTS, UNIT NOS.1 & 2 LICENSE NOS. DPR-71 AND 62 DOCKET NOS. 50-325 AND 50-324 RESPONSE TO IE BULLETIN 80-01

Dear Mr. O'Reilly:

In response to your letter of January ll, 1980, transmitting IE Bulletin 80-1, Carolina Power & Light Company submits the following information.

The Brunswick Plant does have hard-seat check valves. They are Velan stainless steel valves with stellite seats, which are of the spring-to-close type, rather than swing check valves. The valves are not leak tested, but they are inspected and receive routine maintenance on a refueling interval basis.

The entire system from the ADS valve operator through the accumulator and then dowr-to and including the compressors is a redundant, seismic class 1B system. Based upon this qualification, the ADS will be operable under all conditions for which it might be required, including seismic events.

Thi-conclusion and the supporting reasons were transmitted by telephone to members of the staff of the Office of Nuclear Reactor Regulatic:, on January 11, 1980.

Based upon the information presented above, Carolina Power &

Light Company plans no further action on IE Bulletin 80-1.

If you have any further questions, please do not hesitate to contact me.

Very truly yours, B. J. Furr Vice President Nuclear Operations CSB:tma*

cc: Mr. N. C. Moseley

}

k w_

=

411 Fayetteville Street

  • P. O. Box 1551
  • Raleigh, N. C. 27602 8002080 L * *g m --

OW1