ML19262A982

From kanterella
Jump to navigation Jump to search
Forwards LER 79-097/03L-0
Date released: 10/03/2019 Download: ML19262A982


LER 79-097/03L-0:on 791108,during Normal Operation, Circulating Water Pump Motor Failed & Caused Diesel Generator Output Breaker to Reclose on Bus.Caused by Locking Out of Close Signal by Antipump Feature.Plant Mods Planned
ML19262A985
Person / Time
Site: Brunswick 
Issue date: 12/06/1979
From: Tollison A
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19262A985 (2)
Forwards LER 79-097/03L-0
ML19262A981
Person / Time
Site: Brunswick 
Issue date: 12/06/1979
From: Furr B
CAROLINA POWER & LIGHT CO.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML19262A981 (1)