I 00 ENCLOSURE Description of Nonconformance Item Metropolitan Edison Company I

Docket No. 50-289 License No. CPPR-40 One item appears to be in nonconformance with a statement in the Final Safety Analysis Report (FSAR) as identified below:

The FSAR, Volume 2, Section 5.2.2.1, " Concrete:, states in part,

}

" Structural concrete work has been perfor=ed in accordance with i

Specifications for Structural Concrete for Buildings, ACI 301-66 modified as necessary for the more exacting requirements of the Reactor Building."

1.

Section 1405 of ACI 301-66 states in part, "The forms and ex-posed concrete shall be kept continuously wet for at least 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> after placing".

Contrary to the above, it was found that, prior to completion

'of the 48 hour5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> initial drying phase, the upper half of the fourth segment of the containment deme concrete was un-covered, and was cool and dry to the hand while the icwer half was covered with moist burlap and was warm to the hand.

27-Section 1201-of ACI-301-66 state in part, "Immediately following the initial curing and before the concrete has i

I dried, additAonal curing shall be accomplished by one of the

-following materials or methods:

1.

Continuing the method used in initial curing.

2.

Waterproof paper conforming to ASTM C-171.

3.

Other moisture-retaining, coverings as approved."

Contrary to the,above, the upper half of segment No. 4 of the containment dome concrete mass pour was found to have been dry precluding the continuance of additional curing.

1480 348

'e

$91009079f

.---,..-..._m f...,.......

.y,--..--

inO bec:

J. B. Henderson, CO A. Giambusso, CO L. Kornblith, CO R. H. Engelken, CO P. A. Morris, DRL CO Files DR Central Files PDR hal ER NSIC DTIE i,