ML19262A160
| ML19262A160 | |
| Person / Time | |
|---|---|
| Site: | Limerick |
| Issue date: | 09/27/1979 |
| From: | Boyer V PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC |
| To: | Grier B NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I) |
| Shared Package | |
| ML19262A159 | List: |
| References | |
| NUDOCS 7910260456 | |
| Download: ML19262A160 (2) | |
Text
.
P.
PHILADELPHIA ELECTRIC COMPANY 2301 MARKET STREET PHILADELPHI A. PA.19101 12151841 4500 vics nwosm?
Mr. Boyce Grier, Director United States Nuclear Regulatory Commission Office of Inspection and Enforcement, Region I 631 Park Avenue King of Prussia, PA IW 0fs
Subject:
USNRC IE Region I Letter dated August 28, 1979 RE: Site and Office Inspection of June 18-20, 1979 Inspection Report No. 50-352/79-06 5 353/79-06 Limerick Generating Station - Units 1 5 2 File:
QUAL 1-2-2 (352/79-06 and 353/79-06)
Dear Mr. Grier:
In response to the subject letter regarding items identified during the subject inspection of construction activities authori:ed by NRC License Nos. CPPR-106 and -107, we transmit herewith the following:
Attachment I - Response to Appendix A Should you have any questions concerning these items, we would be pleased to discuss them with you.
Sincerely,
~ * +.;.'.,G.
,e
+,,,
i.
V. S. Boyer JMC/mmk Att achment
- 7 262 L
7910260
A.
ATTACHIENT I RESPONSE TO APPENDIX A Item of Noncomuliance Infractiqn_
Appendix 3 of 10CFR50, Criterion V, states, in part:
" Activities affecting quality shall be accomplished in accordance with those instructions, drawings and procedures The Li;erick PSAR, Appendix D, Quality Assurance Program Paragraph D.6.h, states, in part:
"Bechtel Construction Depart =ent is responsible for construction of the plant to approved engineering specifications, drawings and procedures Bechtel Piping System Erection Specification P-322, Revision 1, Paragraph 8.2.1, states, in part:
" Prior to erection of a system, field engineering shall provide data for project engimering review and approval indicating:
(a)
The proposed spool erection sequence.
(b)
The proposed final closure fit-up points."
Contrary to the above as of June 19, 1979, pipe spools for RHR piping (DCA-10h-01) were installed (erected and welded) without the required proposed spool erection sequence and final closure fit-up points having been submitted to Bechtel Project Engineering for review and approval.
Res.:anse to Infraction The pipe spool erection sequence was submitted to Bechtel Project Engineering and approval has been received. This approval covers the actual sequence in which the spools were installed and covers all welds made to date.
In order to avoid further items of noncompliance a review was made of piping systems requiring approved erection sequences and the procedures contnining these sequences have been submitted to Bechtel Project Engineering and have been approved. The approval covers the actual sequence in which the spools were installed and covers all welds made to date.
A training session covering the above subject was held for the responsible Superintendents, Engineers and General Foremen.
7 263 I-1/1 50-352/79-06 50-353/79-06