ARRIGo

,'c UNITED STATES y y,,..tf( g NUCLE AR REGULATORY COMMISSION g

g 5.*/Mi;{M/. c REGION V o,fi.s;j!,L5[o'"[

1990 N. CALIFORNI A BOUL EVARD SutTE 202, WALNU T CREEK PLAZ A

%, +., ' *

~

WALNUi CREE K. C ALIFORNIA 94596 t

a June 26, 1979 Docket !!os. 50-133 50-275 50-323 Pacific Gas anc~ Electric Company 77 Beale Street San Francisco, California 94106 Attention-Mr. Philip A. Crane, Jr.

Assistant General Counsel Gentlemen:

In accordance with our letter dated April 1,1979 transmittino

.; ;.c+in 79-05, we are enclosing Preliminary llotification 79-67AU.

Sincerely, a..-

f h { I s.

s(

2 -.

R. H. Eng31 ken Director

Enclosure:

Pl10-79-67AU cc w/ enclosure:

W. Barr, PG&E W. Raymond, PG&E E. Weeks, PG&E, Humboldt Bay J. D. Worthington, PG&E R. Ramsay, PG&E, Diablo Canyon 9cl L O.c--(

a 7 9 0 7 05 erSl

'1 I

ii i

IMMEDINTE PREI.IMINARY NOTIFICATION June 26, 1979 PRELIMINARY NOTIFICATION OF AN EVENT OR UNU$UAL OCCURRENCE -- P'io-79-67AU This vreliminary notification provides updated information of safety or public interest sty,nificance.

, Facility: Three Mile Island Unit 2 Middletown, Penasylvania (DN-50-320)

Subject:

UPDATED STATUS REPORT Operational:

1.

Ave. age coolant temperature is 154 degrees F.

The highest incore thermocouple temperature indication is 267 degrees F.

Core flow is being provided by natural circulation.

Core co'> ling is being maintained by steaming the "A" Steam Generator to the recit. condenser on the b pass valve. Primary pressure is about 325 psi.

The 3 icensee plans to clculy decrease pr.: asure to about 250 pai.

2.

Daily cteasurements of reactor building water level still indicate 7.010.5 feet above floor level.

3.

The Pressure-Volume Control system is nearing cccipletion.

Coupletion and testing of sy0tems continues to progress slowly, with procurement problems and systea changes being significant contributors.

Envirocmental Status:

Environmental radiation levels re:Aain consistent with natural background levels. Airborne releases have been below Technical Specification limits.

From June 18-24, 35 air samples, 2 r.tilk samples, 4 vegetation saaples and 2 noil samples were collected by the YtC. All analytical results were less than minimum detectable activity (MDA).

EPA air, water and milk sampies collected during the w-ek (up to June 22) choved no detectable activity Irom TriI.

C09TINUFD I px

-. O,

',#\\

/

DUPLICATE DOCUMENT Entire document previously entered into system under:

~ qol030 \\ \\15 xNo

.>ca b'E n.

No. of pages:

i k N.

iC_

m

,m

__ _ ' u as-~

w "'-m

_m..