ML19260D080

From kanterella
Jump to navigation Jump to search
Forwards IE Circular 80-01, Svc Advice for GE Induction Disc Relays. No Response Required
ML19260D080
Person / Time
Site: Summer 
Issue date: 01/17/1980
From: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To: Mary Johnson
SOUTH CAROLINA ELECTRIC & GAS CO.
References
NUDOCS 8002070364
Download: ML19260D080 (2)


Text

/

'o UNITED STATES 8'

e NUCLEAR REGULATORY COMMISSION IoE REGION ll

$4 of E

101 MARIETTA ST., N.W., SUITE 3100 4

8

,o ATLANTA, G EORGIA 30303 JAN 171989 In Reply Refer To:

RII:JPO South Carolina Electric and Gas Company Attn:

M. C. Johnson, Vice President Special Services and Purchasing Post Office Box 764 Columbia, South Carolina 29218 Gentlemen:

The enclosed IE Circular No. 80-01 is forwarded to you for information and if applicable necessary action in accordance to the attached General Electric Company Service Advice 721-162.2.

No written response to this Circular is required.

If you have any questions related to the subject, please contact this office.

Sincerely, N'D-

<t.

Jame7P 0'

Director

Enclosures:

1.

IE Circular No. 80 2.

List of Recently Issued IE Circulars 1937 183 cq s00:020 sot

...w._

4

JAN 171930 South Carolina Electric and Gas Compan;.

cc w/ encl:

T. B. Conners, Jr.

Conners, Moore and Corber 1747 Pennsylvania Avenue, N.W.

Washington, D.C.

20006 A. A. Smith Quality Assurance Post Office Box 8 Jenkinsville, South Carolina 29065 O. S. Bradham, Manager Nuclear Operations Post Offi-: ~,x 8 Jenkinsvili, South Carolina 29065 1937 184

UNITED STATES SSINS No.:

6830 NUCLEAR REGULATORY COMMISSION Accessions No.:

^

OFFICE OF INSPECTION AND ENFORCEMENT 7912190644 WASHINGTON, D.C.

20555 January 17, 1980 IE Circular No. 80-01 SERVICE ADVICE FOR GENERAL ELECTRIC INDUCTION DISC RELAYS Alabama Power Company reported to the NRC on October 16, 1979 a potential problem with certain General Electric Company induction disc type protective relays. A higher than normal pick-up value was caused by petroleum jelly lubricant which under high temperature conditions can migrate to the backstop. At room temper-ature the lubricant can become adhesive and cause pickup values to be higher than setpoint values.

General Electric (GE) laboratory confirmed some higher than normal pickup values and recommended that users determine whether relays meeting the following criteria are in use at their facilities:

(1) Relay type:

IAC, IAV, ICR, or IJCV, AND (2) The relay date code (which is printed on a 3/4" x 3/8" sticker affixed to the relay cradle) has a number less than 50, followed by any of the following two letter codes:

(a) Any first letter followed by H, J, K, L, or M; or (b) The letter combinations AN, BN, CN, DN, EN, DG, EG, FG, GG, HG, JG, KG, LG or MG.

For example, 31GK would be considered, while 50 GK or 23HN would not be considered.

Experience has shown that the cleaning procedure recommended in GE Service Advice 721-162.1 may not in all cases remove all of the petroleum jelly which is lodged in place.

Based on the above, licensees are advised to apply G.E. Service Advice 721-162.2 (Enclosure A) to all relays that fall within the above two criteria.

No written response to this Circular is required.

If you desire additional information regarding this matter contact the Director of the appropriate NRC Regional Office.

Attachment:

GE Service Advice 721-162.2 DUPLICATE DOCUMENT Entire document previously entered into system unde h

h ANO No. of pages: