/03L-0:on 791105,unit Experienced Loss of Essential Instrumentation Distribution Panel Y2 & Did Not Enter Action Statement in Mode 5.Caused by Blown Preinverter YV2 Output Fuse.Repaired Inverter
ML19260B513
Person / Time
Site: Davis Besse 
Issue date: 12/04/1979
From: Naylor R
TOLEDO EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML19260B507 List:
References
LER-79-107-03L, LER-79-107-3L, NUDOCS 7912100288
Download: ML19260B513 (2)


LER-1979-107, /03L-0:on 791105,unit Experienced Loss of Essential Instrumentation Distribution Panel Y2 & Did Not Enter Action Statement in Mode 5.Caused by Blown Preinverter YV2 Output Fuse.Repaired Inverter
Event date:
Report date:
3461979107R03 - NRC Website

text

U. S. NUCLE AR REGULATOR 1f COMMISSION NGC FORM 3GG (71H LICENSEE EVENT REPORT CONTROL BLOCK: l l

l l

l l

l (PLE ASE PRINT OR TYPE ALL REQUIRED INFORMATIONI I

6 l0 lH lD lB lS l1 l@l 0l 0l -l 0l 0l Nl Pl Fl -l 0] 31GL' l il il il 11GI I IG l0 1

24 26 LICENSk TY PE JG b 7 U A T bd 7

8 9 LICENSEE CODE 14 lb LICENSE NUV8EH Q j0 l5 l0 l-10 l3 l4 (6 @l 11 1l 0 l 5l 7 l 9 l@l 1 l 2 l 0 l 4 ] 7 l 9 j@

CON'T "E'

64 tr>

EVENT DATE 14 75 REPORT DATE B0 o

i 3 u cE 00 61 DOCKET NUYBER

?

8 EVENT DESCRIPTION AND PROB ABLE CONSEQUENCES h10 1320 hours0.0153 days <br />0.367 hours <br />0.00218 weeks <br />5.0226e-4 months <br /> tTie unit experienced a loss of essential instru-l On November 5, 1979, at o

2 Being in Mode 5, the unit did not enter the Action [

y j ; mentation distribution panci Y2.

Statement of Technical Specification 3.8.2.2, as it only requires three of the 120 j

g o,,,, g There was no danger to the health and l

volt AC essential buses operable in the mode.

o 3 This occurrence is being reported to docu--l l o is ] l safety of the public or station personnel.

failure.

(NP-33-79-122) l l ment a component o

7 I

80 O

8 l

COMP.

VALVE SYST EM

CAUSE

CAUSE CODE CODE SUBCODE COYPONENT CODE SUBCODE SUBCOLE g

lE lB j@ @@ W@ lE lL lE lC l0 lN [@

Zl@ y@

7 8

9 10 11 12 13 18 1:#

20 R EVISION SEQUENTI AL OCCURRENCE

nPORT

,_ EVENT YE AR REPORT No.

CODE TvPE N O.

O a'ER ROI7 I9 !

!-j l1 0l7l y

l0 l3 l lL l_[

{

L u>$

_2B 22 2J 24 26 27 28 29 30 31 J2 TAK ACTO ON PL A T ET i HOURS 22 SB IT FO UB.

S PLIE MAN FA T HER L^J@lZI@

lZi@

WO 1 010I01 I

W@

lY[g Al@

lCl7l8 2[g 33 34 35 36 31 40 41 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h [Under Maintenance Work Order (>NO) 79-3487, the loss of Y2 was found to be caused by a i

o The blown fuse appears to be related to j

[ blown fuse on the pre-inverter YV2 output.

FNO 79-3504 was written to

_ g,,,, l an open resistor ir the power supply of inverter YV2.

On November 8, 1979, the inverter was tested and returned to j

,,;.,g l repair the inverter.

g,j,j l service.

Investigation is continuing with the vendor.

J 80 7

8 9 ST S

% POWER OTHER STA TUS iSCO RY DISCOVEHY DESCRIPTION l

y B @ l0l0 0 [@l N A l

g gl Operator observation e0 44 4s 12 o

CoTTENT

' ACTiviTv LOCATION OF RELE ASE RELE A0ED OF RELE ASE AMOUNT of ACTIVITY l

l NA

] @ l Z l@l NA i c 80 44 45 7

8 9 to 11 PERSONNEL E MPOSURES NUMPFR TYPE

DESCRIPTION

l LLL7.110101 Ol@lzl@l N^

PE nsONsE t i..;u'niES onCR prion @

w v,ER 10l 0101@l NA

~'

80 i a 7

8 9 11 12 LOSS OF OH D AM ACE TO FACILITY l

TYPE D E SC RIP TIO N

[ Zj@] NA i 9 80 7912100M8 7

8 9 10 NnC Use ONov issUNEL 8l tlCniPrioNO l

l l l l l l l l l l l l ll o

NA 2 o 68 69 FO S 7

8 9 10 DVR 79-159 NAVE OF PREPAHER

TOLEDO EDISON COMPANY DAVIS-BESSE NUCLEAR POWER STATION UNIT ONE SUPPLEMENTAL INFORMATION FOR LER NP-33-79-122_

DATE OF EVENT: November 5, 1979 FACILITY: Davis-Besse Unit 1 Loss of essential instrumentation distribution panel IDENTIFICATION OF OCCURRENCE:

Y2 The unit was in Mode 5, with Power (MNT) = 0, and Conditions Prior to Occurrence:

Load (Gross MWE) = 0.

On November 5, 1979 at 1320 hours0.0153 days <br />0.367 hours <br />0.00218 weeks <br />5.0226e-4 months <br />, the unit experienced Description of Occurrence _:

a loss of essential instrumentation distribution panel Y2 caused by a blown fuse on Being in Mode 5, the unit did not enter the Action the pre-inverter YV2 output.

Statement of Technical Specification 3.8.2.2 as it only requires three of the 120 volt This occurrence is being reported to docu-AC essential buses operable in this mode.

ment a component failure.

The cause of the blown fuse is not yet Designation of Apparent Cause of Occurrence:

fully understood but it appears to be related to an open resistor in the power supply to the inverter.

The resistor functioned as a buffer on the input of inverter YV2.

When open, the output of the inverter fails low causing the loss of the bus.

There was no danger to the health and safety of the public Analysis of Occurrence _1 The unit was shutdown and the three redundant channels or to station personnel.

Essential instrumentation distribu-were operable while the inverter was inoperable.

tion panci Y2 was re-energized from its alternate power source.

79-3487, On November 5, 1979 under Maintenance Work Order (MWO)

Corrective Action

When the an investigation was conducted to determine :he cause of the blown fuse.

On 79-3504 was written to repair the inverter.

open resistor was discovered, MWO Power Engineering November 8, 1979, the inverter was tested and returned to service.

and Construction is investigating the relationship between the open resistor and blown fuse with the vcndor.

There have been previous failures of fuses but non due to buffer Failure Data:

resistor failure.